same type of control. In case of having both controls configured as masters,
the screen of the Daikin control will show the error “88” and the error “U5”
will be sent to the bus.
Take into account:
When switching the type of control of the Daikin wired
control between
master
and
slave,
it is necessary to remove the power
supply from the wired control and connecting it again for rebooting the wired
control in the suitable mode
Important:
The wired control BRC1E51A7 can only operate as master
control. In case of using this model of wired control in the installation, it is
necessary configuring the KLIC-DI as slave control.