KLIC-FJ vT
Technical Support:
15
Flaps
:
enables the fan flaps function. See section 2.4.3.
TEMPERATURE SETPOINT
Figure 10. A/C Gateway. Configuration. Temperature setpoint.
The following objects to control and supervise setpoint temperature will be available by
default:
“[AC] Temperature Setpoint”:
2-Byte object that allow selecting decimal
temperature values that belong to the range [10º-32º].
“[AC] Temperature Setpoint (Status)”
: 2-Byte object that provides the
Temperature setpoint status.
Note
:
A X.Y value will be rounded
to X.0 if [Y < 5] or to X.5 if [Y ≥ 5].
Status object will be updated to the last setpoint temperature value received by the A/C
unit after a complete communication cycle and will be sent to KNX bus every time that
its value changes.
Setpoint limits can be configured by parameter:
Setpoint Limits
: allows restricting the range of the temperature setpoint (from
below in the Cooling, Dry and Auto modes and from above in the Heating and
Auto modes), provided that the limits are still within the predefined limits of the
A/C unit. When KLIC-FJ vT receives an order to send the A/C unit a setpoint
which is greater (or lower) than the configured limits, it will actually send the
limit value.
➢
Minimum (Cooling / Auto / Dry Mode)
: sets the upper limit.
➢
Maximum (Heating / Auto Mode)
: sets the lower limit.