KLIC-FJ vT
Technical Support:
25
For every enabled scene, the particular parameters that should be configured are:
Scene number
: sets the scene number (1-64) that, upon reception through the
scenes object
“
[AC] Scene
” (decreased by one), will trigger the corresponding
orders, as defined next:
On/Off
: “No change” (the state the machine had before the power failure), “On”
or “Off”.
Mode
: “No change”, “Automatic”, “Heating”, “Cooling”, “Fan” or “Dry”.
Fan speed
: “No change”, “Automatic” or any of the available fan speeds (1-4).
Horizontal flaps
: “No change”, “Swing” (if available), “Auto” (if the automatic flap
position control is available) or any of the available flap positions (1-5).
Vertical flaps
: “No change”, “Swing” (if available), “Auto” (if the automatic flap
position control is available) or any of the available flap positions (1-5).
Setpoint
: “No change” or any
value
between 10ºC and 32ºC.
Note
:
this initial setpoint value may be modified by the setpoint limits during
runtime.
2.4.6
ERROR HANDLING
KLIC-FJ vT is capable of managing two error types:
Internal errors:
errors in the communication process between KLIC-FJ vT and
the A/C unit:
➢
Communication error
: KLIC-FJ vT received no response of the A/C unit
during 2 minutes.
There is a LED notification, by which the LED on the device will light green
when the communication error is active.
➢
Control error
: indicates that although there is activity in Fujitsu
communication bus (for example, the master remote wired controller is