KLIC-FJ vT
Technical Support:
10
2.4
A/C GATEWAY
2.4.1
CONFIGURATION
KLIC-FJ vT allows controlling and monitoring an air-conditioning unit in the same way it
would be through the wired remote control it is provided with.
Through the KNX bus, KLIC-FJ vT can be sent orders to control the following basic
functions of the air conditioning unit:
On/Off
switch of the air-conditioning unit.
Operation mode
: automatic, heating, cooling, fan and dry.
Temperature setpoint
, which
can be modified
within a specific range of values,
depending on the capabilities of the specific A/C unit being controlled.
Fan speed
: 3 or 4, depending on the model of the A/C unit.
Control of flaps (or vanes) positioning
: step control, direct positioning and
swing movement of horizontal and vertical flaps, depending on the A/C unit.
Moreover, KLIC-FJ vT allows configuring several advanced functions:
Control configuration:
which allows establishing the type of master-slave
control desired to KLIC-FJ vT.
Error type configuration:
to define error type of the A/C unit.
Setpoint limits
:
to restrict the range for the temperature setpoint.
External reference temperature
: which allows enabling an object to use an
external reference temperature, provided by a temperature probe.
Operating time
: provides in hours the A/C unit operating time.
Automatic off
, which allows an automatic and temporary switch-off of the unit
(after a pre-established delay, if desired) when the communication object
associated to this function is triggered due to a certain event.
Initial configuration
: which allows establishing the desired initial parameters for
the state of the A/C unit after programming or restarting the device.
Scenes
, which
allows defining predefined climate control environments, to be
sent to the machine on the reception of scene orders from the KNX bus.