KLIC-MITT v2
Technical Support:
11
OPERATION MODES
KLIC-MITT v2 allows controlling the A/C unit operating mode through the following
objects, available by default:
“[AC] Mode”
: 1-Byte object which allows selecting the A/C unit operation
mode. There will be only taken in account values that are appropriated with
some of available modes in Mitsubishi Electric units, which are represented in
“[AC] Mode (Status)”
: 1-Byte object which allows knowing the A/C unit
operating mode status.
Object Value
A/C unit mode
0
Auto
1
Heating
3
Cooling
9
Fan only
14
Dry
Table 1.
A/C unit operating modes.
Additionally, a simplified mode can be configured to select Cooling and Heating mode.
Simplified Mode
[
disabled
/enabled
]:
in addition to the “
[AC] Mode
” and
“
[AC] Mode (Status)
” one-byte objects, available by default, it is possible to
commute and to verify the current operation mode through the following one-
bit objects, which get enabled after activating this parameter:
“
[AC] Simplified Mode
”, which allows switching to the Cooling mode by
sendin
g it a “0” and to the Heating mode by sending it a “1”.
“
[AC] Simplified Mode (Status)
”, which will send a value of “0” when the
mode switches to Cooling or to Dry, or a value of “1” when it switches to
Heating. The Fan mode is not reflected in the value of this object.
VENTILATION
Fan
[
disabled
/enabled
]:
enables the Fan function. See section 2.2.2.
Flaps
[
disabled
/enabled
]:
enables the fan Flaps function. See section 2.2.3.