KLIC-MITT v2
Technical Support:
12
TEMPERATURE MEASURED BY THE A/C UNIT
Monitoring
[
disabled
/enabled
]:
enables the
“
[AC] AC Unit Measured
Temperature
” two-byte object, which provides the value of its internal
temperature sensor, which is used by the AC machine to execute the control
loop. Once enabled, a secondary parameter will show:
Sending Type
[
Variation
/ Periodic / Periodic + Variation
]: sets whether
the above object should be sent only in case of a change in the value,
periodically in both cases, respectively. The latter two options bring entail
one more parameter:
Period
[
1…3600
][
s
] [
1…
15
…1440
][
min
] [
1…24
][
h
]: sets the cycle time
for the periodic sending.
Figure 6.
AC Gateway. Configuration. Temperature measured by the AC unit.
TEMPERATURE SETPOINT
The following objects to control and supervise setpoint temperature will be available by
default:
“[AC] Temperature Setpoint”:
2-Byte object that allow selecting decimal
temperature values that belong to the range [16º-31º].
“[AC] Temperature Setpoint (Status)”
: 2-Byte object that provides the
Temperature setpoint status.
Note
:
A X.Y value will be rounded to X.0 if [Y < 5] or to X.5 if [Y ≥ 5].
Status object will be updated to the last setpoint temperature value received by the A/C
unit after a complete communication cycle and will be sent to KNX bus every time that
its value changes.