KLIC-MITT v2
Technical Support:
19
Step Control (1 Bit)
[
disabled
/enabled
]:
enables the
“
[AC] Fan: Step Control
”
one-bit object
for increasing (value “1”) or decreasing (value “0”) the current
speed level sequentially.
This sequence can be either
“Cyclical” (a further step once reaching the
maximum level activates the minimum level again) or
“
Non Cyclical
”.
Figure 12.
Cyclical fan step control (three fan speeds without automatic mode
).
Figure 13.
Non-cyclical fan step control (three fan speeds without automatic mode
).
In case of having enabled the
automatic mode
, the control sequence will differ:
Non-cyclical
: the automatic mode will be placed before the minimum speed
(speed 1):
Auto
↔ Minimum ↔ … ↔ Maximum
.
Cyclical
: the automatic mode will be placed between the maximum speed
(speed n) and the minimum speed (speed 1):
Auto
↔ Minimum ↔ … ↔
Maximum ↔ Auto ↔ Minimum ↔ …