ANNEX I. COMMUNICATION OBJECTS
“Functional range
” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a
particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
Number
Size
I/O
Flags
Data type (DPT)
Functional Range
Name
Function
1
1 Byte
I/O
C T R W U
DPT_SceneControl
0-63; 128-191
[AC] Scene
0 - 63 (Execute 1 - 64); 128 - 129 (Save
1 - 64)
2
1 Bit
I
C - - W -
DPT_Switch
0/1
[AC] On/Off
0 = Off; 1 = On
3
1 Bit
O
C T R - -
DPT_Switch
0/1
[AC] On/Off (Status)
0 = Off; 1 = On
4
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00° - 670760.00°
[AC] Temperature Setpoint
[16 ... 31] ºC
5
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00° - 670760.00°
[AC] Temperature Setpoint (Status)
[16 ... 31] ºC
6
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00° - 670760.00°
[AC] Temperature Setpoint: Upper Limit
[16 ... 31] ºC
7
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00° - 670760.00°
[AC] Temperature Setpoint: Upper Limit
(Status)
[16 ... 31] ºC
8
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00° - 670760.00°
[AC] Temperature Setpoint: Lower Limit
[16 ... 31] ºC
9
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00° - 670760.00°
[AC] Temperature Setpoint: Lower Limit
(Status)
[16 ... 31] ºC
10
1 Byte
I
C - - W -
DPT_HVACContrMode
0 = Auto
1 = Heat
3 = Cool
9 = Fan
14 = Dry
[AC] Mode
0 = Automatic; 1 = Heating; 3 = Cooling;
9 = Fan; 14 = Dry
11
1 Byte
O
C T R - -
DPT_HVACContrMode
0 = Auto
1 = Heat
3 = Cool
9 = Fan
14 = Dry
[AC] Mode (Status)
0 = Automatic; 1 = Heating; 3 = Cooling;
9 = Fan; 14 = Dry
12
1 Bit
I
C - - W -
DPT_Heat_Cool
0/1
[AC] Simplified Mode
0 = Cooling; 1 = Heating
13
1 Bit
O
C T R - -
DPT_Heat_Cool
0/1
[AC] Simplified Mode (Status)
0 = Cooling; 1 = Heating
14
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
[AC] Fan: Percentage Control
[0]% = Automatic; [0.4...50.2]% = S1;
[50.6...100]% = S2
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
[AC] Fan: Percentage Control
[0.4...50.2]% = S1; [50.6...100]% = S2
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
[AC] Fan: Percentage Control
[0]% = Automatic; [0.4...33.3]% = S1;
[33.7...66.7]% = S2; [67.1...100]% = S3
1 Byte
I
C - - W -
DPT_Scaling
0% - 100%
[AC] Fan: Percentage Control
[0.4...33.3]% = S1; [33.7...66.7]% =