Figure 10.
A/C Gateway. Configuration. Temperature setpoint.
Once these limits are enabled, several objects to modify them at run time will be
available. The values of this objects will be restricted to an interval which is defined by
the absolute limits established by the A/C unit (16ºC to 30ºC).
“[AC] Temperature Setpoint: Lower Limit”
: 2-Byte object that allows
changing the lower limit at run time.
“[AC] Temperature Setpoint: Lower Limit (Status)”
: 2-Byte object with the
lower limit current value.
“[AC] Temperature Setpoint: Upper Limit”
: 2-Byte object that allows
changing the upper limit at run time.
“[AC] Temperature Setpoint: Upper Limit (Status)”
: 2-Byte object with the
upper limit current value.
Notes
:
If [Minimum] ≥ [Maximum], limits will not be taken in account in Auto mode due
to the incongruity. In this case, default values will be used.
These parameters only can be set as integer values in ETS. However, at run
time the associated objects allow decimal values.
The A/C unit set a fixed temperature setpoint of 24ºC in Fan mode and will
ignore any setpoint temperature value received.
The setpoint limits set by the A/C unit on each operating mode are indicated in
Table 2, however, these limits can be more restrictive changing the
configuration with the wired remote control: