KLIC-SG vT
Technical Support:
21
Control Value
Status Value
Level sent to the A/C unit
0%
0%
0 (auto)
1-33%
33%
1 (low)
34-66%
66%
2 (medium)
67-100%
100%
3 (high)
Table 3.
Fan Speed for 3 levels of ventilation.
Notes
:
In automatic mode, it is not possible to know the effective fan speed, so,
when this mode is activated, fan speed status will remain at 0% value.
In Dry and Auto mode, A/C unit sets fan speed in automatic mode. Due to
this fact, fan speed control orders will be ignored during this mode. On the
other hand, in Fan mode is not possible to send fan speed 0% (auto).
Step Control (1 bit)
[
disabled
/enabled
]: enables the
“[AC] Fan: Step
Control”
one-bit object. If the parameter is enabled, the following options are
displayed:
Non Cyclical
: the automatic mode will be ahead the minimum speed
(speed 1):
Auto
↔ Minimum ↔ … ↔ Maximum.
Cyclical
: the automatic mode will be between the maximum speed (speed
n) and the minimum speed (speed 1):
Auto
↔ Minimum ↔ … ↔
Maximum ↔ Auto ↔ Minimum ↔ …
Automatic fan speed mode
can also be activated through a one-bit object that will
appear activating the following parameter:
Individual Object for Automatic Mode
[
disabled
/enabled
]
:
enables the “
[AC]
Fan: Automatic
” and “
[AC] Fan: Automatic (Status)
” one-bit objects, which
Control Value
Status Value
Level sent to the A/C unit
0%
0%
0 (auto)
1-25%
25%
1 (low)
26-50%
50%
2 (medium)
51-75%
75%
3 (high)
76-100%
100%
4 (turbo)
Table 4.
Fan Speed for 4 levels of ventilation.