KLIC-SG
Technical Support:
10
2.2
A/C GATEWAY
2.2.1
CONFIGURATION
KLIC-SG allows controlling and monitoring an air-conditioning unit in the same way it
would be through the wired remote control it is provided with.
Through the KNX bus, KLIC-SG can be sent orders to control the following basic
functions of the air conditioning unit:
On/Off
switch of the air-conditioning unit.
Operation mode
: automatic, heating, cooling, fan and dry.
Temperature setpoint
, which
can be modified
within a 16-30ºC range.
Fan speed
: 3 or 4 levels, depending on the model of the A/C unit.
Moreover, KLIC-SG allows configuring several advanced functions:
Simplified Operation Mode
, which allows switching between heating and
cooling operation modes by means of a 1-bit object.
Fan
, which allows advanced configuration of the ventilation, see section 2.2.2.
Temperature measured by the AC unit
, which
allows enabling an object
which provides the value of the internal temperature probe. The automatic
sending can be configured based on: a period of time, a change in value or a
combination of both.
External reference temperature
, which allows enabling an object to use an
external reference temperature, provided by a temperature probe.
Setpoint limits
, to restrict the range for the temperature setpoint.
Automatic off
, which allows an automatic and temporary switch-off of the unit
(after a pre-established delay, if desired) when the communication object
associated to this function is triggered due to a certain event.