KLIC-SG
Technical Support:
17
Mode
Temperature Setpoint
Auto
[18º-30º]
Cooling
[18º-30º]
Heating
[16º-30º]
Fan
Not available
Dry
[18º-30º]
Table 2.
Interior setpoint limits of A/C unit
AUTOMATIC OFF
Figure 11.
A/C Gateway. Configuration. Automatic off.
Automatic Off
[
disabled
/enabled
]
:
enables the “
[AC] Automatic Off
” and
“
[AC] Automatic Off (Status)
” binary objects, which lets performing a
temporary switch-
off of the A/C unit by sending it a value of “1” and a later
switch-
on by sending it a value of “0”. This object will be typically linked to a
window sensor or a similar event trigger. Automatic off will be also active if the
unit is previously in off state, so, the unit will not be able of being on until this
situation finishes.
During the temporary switch-off state, KLIC-SG will still monitor any control
orders being received (setpoint, fan speed, etc.), so they can be applied once
it leaves such state.
Automatic Off Object Polarity
[
0 = Activate; 1 = Deactivate /
0 =
Deactivate; 1 = Activate
]: sets the polarity of the above object.
Automatic Off Delay
[
1…
60
…3600
] s: sets the time KLIC-SG waits before
switching the A/C machine off. Any switch-off order received during the
delay will abort the time count. This delay can be changed at run time by
using the object “
[AC] Automatic Off: Delay
”. Sending the value “0”
disables the Automatic Off functionality.