KLIC-SG
Technical Support:
33
14
1 Byte
I
C - W - -
DPT_Scaling
0% - 100%
[AC] Fan: Percentage Control
0% = Auto; [0,4..25,1]% = S1;
[25,5..50,2]% = S2; [50,6..75,3]
% = S3; [75,5..100]% = S4
1 Byte
I
C - W - -
DPT_Scaling
0% - 100%
[AC] Fan: Percentage Control
0% =Auto; [0,4...33.33] % = S1;
[33.73...66.67] % = S2;
[67.06...100] % = S3
15
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[AC] Fan: Percentage Control (Status)
Auto = 0%; S1 = 25,1%; S2 =
50,2%; S3 = 75,3%; S4 = 100%
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[AC] Fan: Percentage Control (Status)
Auto = 0%; S1 = 33.33%; S2 =
66.67%; S3 = 100%
16
1 Bit
I
C - W - -
DPT_Enable
0/1
[AC] Fan: Automatic
0 = Automatic On; 1 = Automatic
Off (Speed 1)
1 Bit
I
C - W - -
DPT_Enable
0/1
[AC] Fan: Automatic
0 = Automatic Off (Speed 1); 1 =
Automatic On
17
1 Bit
O
C R - T -
DPT_Enable
0/1
[AC] Fan: Automatic (Status)
0 = Automatic On; 1 = Automatic
Off
1 Bit
O
C R - T -
DPT_Enable
0/1
[AC] Fan: Automatic (Status)
0 = Automatic Off; 1 = Automatic
On
18
1 Bit
I
C - W - -
DPT_Step
0/1
[AC] Fan: Step Control
0 = Down; 1 = Up
19
1 Bit
O
C R - T -
DPT_Bool
0/1
[AC] Fan: Protection Stop
0 = Normal operation; 1 = Stop
protection activated
1 Bit
O
C R - T -
DPT_Bool
0/1
[AC] Fan: Protection Stop
0 = Stop protection activated; 1 =
Normal operation
20
1 Byte
I
C - W - -
DPT_Value_1_Ucount
0 - 255
[AC] 360 CST Air Flow
0 = Spot; 1 = Mid; 2 = Wide; 3 =
Swing
21
1 Byte
O
C R - T -
DPT_Value_1_Ucount
0 - 255
[AC] 360 CST Air Flow (Status)
0 = Spot; 1 = Mid; 2 = Wide; 3 =
Swing
22
1 Bit
I
C - W - -
DPT_Switch
0/1
[AC] Horizontal Flaps: Swing
0 = Swing Off; 1 = Swing On
1 Bit
I
C - W - -
DPT_Switch
0/1
[AC] Horizontal Flaps: Swing
0 = Swing On; 1 = Swing Off
23
1 Bit
O
C R - T -
DPT_Switch
0/1
[AC] Horizontal Flaps: Swing (Status)
0 = Swing Off; 1 = Swing On
1 Bit
O
C R - T -
DPT_Switch
0/1
[AC] Horizontal Flaps: Swing (Status)
0 = Swing On; 1 = Swing Off
24
1 Bit
I
C - W - -
DPT_Switch
0/1
[AC] Vertical Flaps: Swing
0 = Swing Off; 1 = Swing On
1 Bit
I
C - W - -
DPT_Switch
0/1
[AC] Vertical Flaps: Swing
0 = Swing On; 1 = Swing Off
25
1 Bit
O
C R - T -
DPT_Switch
0/1
[AC] Vertical Flaps: Swing (Status)
0 = Swing Off; 1 = Swing On
1 Bit
O
C R - T -
DPT_Switch
0/1
[AC] Vertical Flaps: Swing (Status)
0 = Swing On; 1 = Swing Off
26
2 Bytes
I
C - W - -
DPT_Value_Temp
-273.00º - 670433.28º
[AC] External Reference Temperature
[0 ... 70] ºC
27
2 Bytes
O
C R - T -
DPT_Value_Temp
-273.00º - 670433.28º
[AC] AC Unit Mesaured Temperature
Temperature from the internal
sensor (ºC)
28
1 Bit
I
C - W - -
DPT_Switch
0/1
[AC] Automatic Off
0 = Deactivate; 1 = Activate
1 Bit
I
C - W - -
DPT_Switch
0/1
[AC] Automatic Off
0 = Activate; 1 = Deactivate
29
1 Bit
O
C R - T -
DPT_Switch
0/1
[AC] Automatic Off (Status)
0 = Deactivated; 1 = Activated