KLIC-SG
Technical Support:
35
61
1 Byte
C - - T -
DPT_Value_1_Ucount
0 - 255
[ERV] Fan: Step
62
2 Bytes
C - - T -
DPT_Value_Humidity
-12% - 12%
[ERV] Outdoor Humidity
63, 67
2 Bytes
O
C R - T -
DPT_Value_Temp
-273.00º - 670433.28º
[Ix] Current Temperature
Temperature Sensor Value
64, 68
1 Bit
O
C R - T -
DPT_Alarm
0/1
[Ix] Overcooling
0 = No Alarm; 1 = Alarm
65, 69
1 Bit
O
C R - T -
DPT_Alarm
0/1
[Ix] Overheating
0 = No Alarm; 1 = Alarm
66, 70
1 Bit
O
C R - T -
DPT_Alarm
0/1
[Ix] Probe Error
0 = No Alarm; 1 = Alarm
71, 77
1 Bit
I
C - W - -
DPT_Enable
0/1
[Ix] Input Lock
0 = Unlock; 1 = Lock
72, 78
1 Bit
C - - T -
DPT_Switch
0/1
[Ix] [Short Press] 0
Sending of 0
1 Bit
C - - T -
DPT_Switch
0/1
[Ix] [Short Press] 1
Sending of 1
1 Bit
I
C - W T -
DPT_Switch
0/1
[Ix] [Short Press] 0/1 Switching
Switching 0/1
1 Bit
C - - T -
DPT_UpDown
0/1
[Ix] [Short Press] Move Up Shutter
Sending of 0 (Up)
1 Bit
C - - T -
DPT_UpDown
0/1
[Ix] [Short Press] Move Down Shutter
Sending of 1 (Down)
1 Bit
C - - T -
DPT_UpDown
0/1
[Ix] [Short Press] Move Up/Down
Shutter
Switching 0/1 (Up/Down)
1 Bit
C - - T -
DPT_Step
0/1
[Ix] [Short Press] Stop/Step Up Shutter
Sending of 0 (Stop/Step Up)
1 Bit
C - - T -
DPT_Step
0/1
[Ix] [Short Press] Stop/Step Down
Shutter
Sending of 1 (Stop/Step Down)
1 Bit
C - - T -
DPT_Step
0/1
[Ix] [Short Press] Stop/Step Shutter
(Switched)
Switching of 0/1 (Stop/Step
Up/Down)
4 Bit
C - - T -
DPT_Control_Dimming
0x0 (Stop)
0x1 (Dec. by 100%)
...
0x7 (Dec. by 1%)
0x8 (Stop)
0xD (Inc. by 100%)
...
0xF (Inc. by 1%)
[Ix] [Short Press] Brighter
Increase Brightness
4 Bit
C - - T -
DPT_Control_Dimming
0x0 (Stop)
0x1 (Dec. by 100%)
...
0x7 (Dec. by 1%)
0x8 (Stop)
0xD (Inc. by 100%)
...
0xF (Inc. by 1%)
[Ix] [Short Press] Darker
Decrease Brightness
4 Bit
C - - T -
DPT_Control_Dimming
0x0 (Stop)
0x1 (Dec. by 100%)
...
0x7 (Dec. by 1%)
0x8 (Stop)
0xD (Inc. by 100%)
...
0xF (Inc. by 1%)
[Ix] [Short Press] Brighter/Darker
Switch Bright/Dark