SAFETY INSTRUCTIONS AND ADDITIONAL NOTES 

 Installation should only be performed by qualified professionals according to the laws and regulations applicable in each country. 

 Do not connect the mains voltage nor any other external voltage to any point of the KNX bus; it would represent a risk for th e entire 

KNX system. The facility must have enough insulation between the mains (or auxiliary) voltage and the KNX bus or the wires of other 
accessories, in case of being installed. 

 The  facility  must  be  equipped  with  a  device  that  ensures  the  omnipolar  sectioning.  Installation  of  a  10 A  mini-circuit-breaker  is 

recommended. To prevent accidents, it must remain open in case of manipulation of the device. 

 Once the device is installed (in the panel or box), it must not be accessible from outside. 

 Keep the device away from water (condensation over the device included) and do not cover it with clothes, paper or any other material 

while in use. 

 The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the instructi ons at 

https://www.zennio.com/en/legal/weee-regulation. 

OUTPUTS SPECIFICATIONS AND CONNECTIONS 

CONCEPT 

DESCRIPTION 

Number of outputs 

Output type 

Solid state switching device 

Maximum load per output 

1000 mA 

Output currents 

220 mA,  300 mA,  350 mA,  500 mA,  550 mA,  630 mA,  700 mA,  750 mA, 
900 mA or 1000 mA. 

Load type 

Constant Current LED load 

Short-circuit protection 

YES 

Overload protection 

NO 

Overheating protection 

YES 

Connection method 

Screw terminal block (0.2 Nm max.) 

Cable cross-section 

0.2-1.5 mm² (IEC) / 16-30 AWG (UL) 

 

EXTERNAL POWER SUPPLY SPECIFICATIONS AND CONNECTIONS 

CONCEPT 

DESCRIPTION 

Voltage 

12-30 VDC 

Current 

4000 mA 

Connection method 

Pluggable screw terminal block (0.4 Nm max.) 

Cable cross-section 

0.5-2.5 mm² (IEC) / 28-12 AWG (UL) 

 

WIRING AND ASSEMBLY DIAGRAMS 

 
 

LED 

Each LED load must be connected according to its positive and the negative terminals. Respect always 
the maximum current allowed by the loads.    

Correspondence 
1

: Red       

2

: Green       

3

: Blue       

4

: White       

+: 

Positive terminal       

-:

 Negative terminal 

 

       

External power supply: 

+  and  -  terminals  of  external  power  supply  (

constant 

voltage)

 from 12 to 30 VDC. 

It is  recommended  to  use  the  closest  external  power 
supply value to the load working voltage

.  

Assembly: 

Screw  mounting,  2  holes  of 
3.5 mm  diameter.  Screws  not 
included. 

 

SEVERAL LOADS CONNECTED TO THE SAME OUTPUT

 

Power  restriction

:  It  is  mandatory  to  fulfil  the  next  restriction 

regarding the power connected to one output channel:

 

𝐼

𝑂𝑢𝑡

× 30

 

𝑉𝑑𝑐 ≥ 𝑁

𝐿𝑜𝑎𝑑𝑠

× 𝑃

𝐿𝑜𝑎𝑑

 

 

OUTPUT CURRENT SELECTOR SWITCH 

 

*it  is  mandatory  that  the  output  current  chosen  by  ETS 
parameter and the current selected with the switch match

. On 

the contrary, the load cannot be controlled and the test LED will 
blink in white. 

TEST LED ERROR IDENTIFICATION  

 

Depending on the color, the test LED indicates different errors: 
 

Color 

Error 

Blinking white 

Output current selection  

Blinking orange 

No auxiliary power supply detected 

Continuous orange 

Wrong auxiliary power supply polarization 

Blinking red 

Overheating level 1 

Continuous red 

Overheating level 2 

 

Right load wiring 

 

 

Wrong load wiring 

 

 

Important  warning: 

the  following  rules  when  not 

considered may result in load or device irreversible 
damages

 

 

Reviews: