SAFETY INSTRUCTIONS AND ADDITIONAL NOTES 

 Installation should only be performed by qualified professionals according to the laws and regulations applicable in each cou ntry. 

 Do not connect the mains voltage nor any other external voltage to any point of the KNX  bus; it would represent a risk for the entire 

KNX system. The facility must have enough insulation between the mains (or auxiliary) voltage and the KNX bus or the wires of other 
accessories, in case of being installed. 

 Once the device is installed (in the panel or box), it must not be accessible from outside. 

 Keep the device away from water (condensation over the device included) and do not cover it with clothes, paper or any other material 

while in use. 

 The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the instructions at 

https://www.zennio.com/en/legal/weee-regulation. 

 This device contains software subject to specific licences. For details, please refer to http://zennio.com/licenses. 

OUTPUTS SPECIFICATIONS AND CONNECTIONS 

CONCEPT 

DESCRIPTION 

Number of outputs 

24 

Output type / Disconnection type 

Potential-free  outputs  through  bistable  relays  with  tungsten  pre-contact  / 
Micro-disconnection 

Rated current per output 

AC 16(6) A @ 250 VAC (4000 VA) 
DC 7 A @ 30 VDC (210 W) 

Maximum load per output 

Resistive 

4000 W 

Inductive 

1500 VA 

Maximum inrush current 

800 A/200 

μs 

165 A/20 ms 

Connections in adjacent outputs  

Possibility of connecting different phases. It is not allowed to connect power 
supplies of different order, SELV with NO SELV, in the same block.  

Maximum current per block 

40 A 

Short-circuit protection 

NO 

Overload protection 

NO 

Connection method 

Screw terminal block (0.5 Nm max.) 

Cable cross-section 

1.5-4 mm² (IEC) / 26-10 AWG (UL) 

Outputs per common 

Maximum response time 

10 ms 

Mechanical lifetime (min. cycles) 

3 000 000 

Electrical lifetime (min. cycles)

100000 @ 8 A / 25000 @ 16 A (VAC) 

¹ Lifetime values could change depending on the load type. 

 

 In order to ensure the expected 

status of the relays, please check 
that the device is connected to the 
KNX  bus  before  energizing  the 
power circuit. 
 

WIRING DIAGRAMS 

A1

A2

L

N

A1

A2

L1

N

L2

A1

A2

L1

N

M

A1

A2

B1

B2

I

II

III

L

N

Figure 2: Wiring example (from left to right): 2 loads, 2 loads 

connected to different phases, shutter and fan coil 

Figure 3: Mounting MAXinBOX 24 v2 

on DIN rail 

Attaching MAXinBOX 24 v2 to DIN rail: 

Removing MAXinBOX 24 v2 from DIN rail:

 