MAXinBOX FC 0-10V FAN
http://www.zennio.com
Technical Support:
http://support.zennio.com
15
15
After enabling any of them, two objects are included by default:
“
[AOx] Output Value (Control)
”: this object is supposed to receive
percentage values from the KNX bus, making the device generate a voltage
output between 0 V and 10 V (proportional to the percentage value).
“
[AOx] Output Value (Status)
”: status object that shows, in terms of
percentage, the current value of the analogue output signal. This object is
automatically sent to the bus after receiving a new voltage setpoint, and when
the output status changes due to a lock order.
The following parameters can be configured from the corresponding tab:
Figure 7
0-10V Analog Output X
– Configuration (in detail).
Enable Lock by Object
: when this checkbox is marked, the one-bit object
“
[AOx] Lock
” turns visible, as well as one more parameter:
➢
Lock Action
: sets the particular state (
“No Change” / “On” / “Off”) the
output will adopt
upon the reception of the value “1” through the “
[AOx]
Lock
” object. If set to “On”, the desired
Output Value
needs to be
configured, in terms of percentage.
Note
:
while an output is locked, further voltage setpoints are ignored (the
device will respond with the current status of the output).