The action performed depends on the output type and, in the case of 0-10V analogue
outputs, on the press type. For both outputs types, the presses have no effect if the
output is disabled in parameters.
Binary output
: a
simple press (short or long) will make the output switch its
on-off state, with independence of the state of the other binary outputs. This
will be reported to the KNX bus through the corresponding status object, if
enabled.
0-10V analogue output
: the action depends on the type of press:
➢
Short press: it is equivalent to a 0% or 100% regulation order through the
“
[AOx] Output Value (Control)
”, causing a 0V or 10V output signal. If the
current state is greater than 0% the regulation order will be 0% (0V), while
if the current state is 0% the regulation will be 100% (10V).
➢
Long press: if the button is long-pressed, the actuator will start increasing
or decreasing the fan speed progressively as long as the button is being
held. The direction of the regulation with every new long press will be
downwards (i.e., a decrease of the fan speed), unless the current state is
0% (in such case, the regulation will consist in an increase). The updated
state object will be sent once the button is released, or when the maximum
/ minimum value is reached. The complete regulation cycle (0% to 100%
or vice versa) takes 10 seconds.
Disabled output
: outputs disabled in parameters will not react to button
presses under the Test Off mode.
Regarding the lock, timer, alarm and scene functions the device will behave under the
Test Off mode as usual. Button presses during this mode are entirely analogous to the
reception of the corresponding orders from the KNX bus.
Test On Mode
After entering the Test On mode, it will only be possible to control the outputs through
the on-board pushbuttons. Orders received through communication objects will be
ignored, with independence of the output they are addressed to.