MAXinBOX FC 0-10V FAN
http://www.zennio.com
Technical Support:
http://support.zennio.com
349, 352
1 Byte
I
C - - W U
DPT_Scaling
0% - 100%
[AOx] Output Value (Control)
0 - 100 %
350, 353
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[AOx] Output Value (Status)
0 - 100 %
351, 354
1 Bit
I
C - - W U
DPT_Enable
0/1
[AOx] Lock
0 = Unlock; 1 = Lock
355, 370
1 Bit
I
C - - W U
DPT_Switch
0/1
[FCx] On/Off
0 = Off; 1 = On
356, 371
1 Bit
O
C T R - -
DPT_Switch
0/1
[FCx] On/Off (Status)
0 = Off; 1 = On
357, 372
1 Bit
I
C - - W U
DPT_Heat_Cool
0/1
[FCx] Mode
0 = Cool; 1 = Heat
358, 373
1 Bit
O
C T R - -
DPT_Heat_Cool
0/1
[FCx] Mode (Status)
0 = Cool; 1 = Heat
359, 374
1 Bit
O
C T R - -
DPT_Switch
0/1
[FCx] Valve Control
0 = Open Valve; 1 = Close Valve
1 Bit
O
C T R - -
DPT_Switch
0/1
[FCx] Valve Control
0 = Close Valve; 1 = Open Valve
1 Bit
O
C T R - -
DPT_Switch
0/1
[FCx] Valve Control (Cooling)
0 = Close Valve; 1 = Open Valve
1 Bit
O
C T R - -
DPT_Switch
0/1
[FCx] Valve Control (Cooling)
0 = Open Valve; 1 = Close Valve
360, 375
1 Bit
O
C T R - -
DPT_Switch
0/1
[FCx] Valve Control (Heating)
0 = Open Valve; 1 = Close Valve
1 Bit
O
C T R - -
DPT_Switch
0/1
[FCx] Valve Control (Heating)
0 = Close Valve; 1 = Open Valve
361, 376
1 Bit
I/O
C T R W
U
DPT_Enable
0/1
[FCx] Forced Position
0 = Disable; 1 = Enable
362, 377
1 Bit
I
C - - W U
DPT_Switch
0/1
[FCx] Manual Fan Control
0 = Disable; 1 = Enable
363, 378
1 Bit
O
C T R - -
DPT_Switch
0/1
[FCx] Manual Fan Control (Status)
0 = Disabled; 1 = Enabled
364, 379
1 Byte
I
C - - W U
DPT_Scaling
0% - 100%
[FCx] Control Variable (Cooling)
0 - 100 %
365, 380
1 Byte
I
C - - W U
DPT_Scaling
0% - 100%
[FCx] Control Variable (Heating)
0 - 100 %
366, 381
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[FCx] Fan Speed
0 - 100 %
367, 382
1 Byte
I
C - - W U
DPT_Scaling
0% - 100%
[FCx] Fan Speed when Valve Closed
(Cooling)
0 - 100 %
368, 383
1 Byte
I
C - - W U
DPT_Scaling
0% - 100%
[FCx] Manual Fan Control Variable
0 - 100 %
369, 384
2 Bytes
I/O
C T R W
U
DPT_TimePeriodMin
0 - 65535
[FCx] Duration of Manual Control
0 = Endless; 1 - 1440 min
2 Bytes
I/O
C T R W
U
DPT_TimePeriodHrs
0 - 65535
[FCx] Duration of Manual Control
0 = Endless; 1 - 24 h
385
1 Bit
C T - - -
DPT_Trigger
0/1
[Heartbeat] Object to Send '1'
Sending of '1' Periodically
386
1 Bit
I
C - - W -
DPT_Switch
0/1
[ML] Trigger
Trigger the Master Light Function
387, 388, 389, 390,
391, 392, 393, 394,
395, 396, 397, 398
1 Bit
I
C - - W -
DPT_Switch
0/1
[ML] Status Object x
Binary Status
399
1 Bit
O
C T R - -
DPT_Switch
0/1
[ML] General Status
Binary Status
400
1 Bit
C T - - -
DPT_Switch
0/1
[ML] General Switch Off: Binary Object
Switch Off Sending
401
1 Byte
C T - - -
DPT_Scaling
0% - 100%
[ML] General Switch Off: Scaling
0-100%
402
1 Byte
C T - - -
DPT_SceneControl
0-63; 128-191
[ML] General Switch Off: Scene
Scene Sending
403
1 Byte
C T - - -
DPT_HVACMode
1=Comfort
2=Standby
[ML] General Switch Off: HVAC mode
Auto, Comfort, Standby, Economy, Building
Protection