Z41 Pro / Lite / COM
http://www.zennio.com
Tecnical Support:
http://support.zennio.com
104
➢
“Enumeration”: integer values are sent through the one-byte object “
[Btn]
[X] Fan control enumerated
”.
Cyclical
: sets whether scrolling through the speed levels is circular or not. If
checked, an increase order in the maximum level switches to the minimum and
vice versa (in the minimum level a decrease order switches to the maximum).
Auto Mode
: sets whether the fan Auto mode will be available or not. If checked,
the following parameters are also shown.
➢
Dedicated Object for Auto Mode
: sets how the Auto mode should be
activated. In the absence of a dedicated object, the Auto fan mode will be
activated by switching to fan level 0.
Figure 96
Fan Control
– Auto Mode.
In this case
(supposing that Speed Levels has been set to “3”), the fan levels
that can be navigated through short presses are:
Auto ( 0 )
Minimum
Medium
Maximum
On the other hand, marking the checkbox enables the one-bit object
“
[Btn] [X] Fan control
– Auto mode
”, which will trigger the Auto mode when
it receives the value “1” (or “0”, depending on the subsequent parameter “
Value
to Set the Auto Mode
”).
Figure 97
Fan Control
– Dedicated Object for Auto Mode.