Figure 98
Special Mode Control (Box)
Figure 99
Special Modes
When this function is assigned to the box, two 1-byte objects (
[Pn][Bi] Special Mode
Control
as the control object, and
[Pn][Bi] Special Mode Indicator
as the status object)
will be enabled. The former will be sending the bus the value that corresponds to the
mode that the user selects by touching the buttons (see Table 6), while the status object
(which can receive values from the bus although it gets self-updated as well on button
presses) will determine the indicative icon represented in the box at any time. If this
object receives an unrecognised value from the bus, no icon will be displayed in the
indicator.
Special Mode
Icon
Object Value
Comfort
1 (0x001)
Standby
2 (0x002)
Economy
3 (0x003)
Protection
4 (0x004)
Auto Mode
5 (0x005)
Table 6
Special Modes vs. Icon vs. Object Value
The remaining parameters for this function are: