Z41 Pro / Lite / COM
http://www.zennio.com
Tecnical Support:
http://support.zennio.com
107
Allow Protection Mode
: this parameter permits excluding
(“No”, default option)
or including
(“Yes”) the “building protection” mode from the special modes listed
in the sequential scrolling performed by the buttons.
Allow Auto Mode
: this parameter permits excluding (“No”, default option) or
including (“Yes”) the “auto” mode from the special modes listed in the sequential
scrolling performed by the buttons.
Left Button
and
Right Button
: permit selecting the icon that will be displayed
inside the buttons in the box.
Note
: a list with a
ll icons available can be found in document “Z41 Icon list”,
available at
www.zennio.com
.
3.6.2.5
OTHER
This category involves the following functions, which can be selected through the
Function
parameter.
3.6.2.5.1
RGB
This function is intended for sending orders to thee-colour LED light regulators, such as
LUMENTO X3 RGB from Zennio.
Figure 100
RGB
When the function is assigned to the box, the following parameters come up:
Object Type
: permits selecting what type of object will be used for controlling the
light level of the RGB channels. It may be
“Three single colour objects (DPT
5.001)
” (by default) or “One RGB object (DPT 232.600)”. If the former is selected,
three 1-byte objects will be enabled (with their
Write
and
Read
flags activated,