Sensor Calibration
: permits setting a certain correction over the values thrown
by the internal temperature probe. This way, if the value of the measurement
is found to be slightly over (or below) the actual temperature due to external
factors, it is possible to set an adjustment between -5.0ºC and 5.0ºC (0.0ºC by
default), in steps of 0.1ºC. The value set here may be optionally changed, in
runtime, from the Configuration page (see section 2.3).
Sending Period
: cycle time (in tens of a second) for sending the value of the
measured temperature to the bus. This sending is made through the
[General]
Internal temperature
object (see section 3.1), enabled by default. The
permitted values are 0 to 100 tens of a second. The value
“0” (set by default)
deactivates this sending to the bus.
Send with a Temperature Change
: permits performing a specific sending of
the temperature value to the bus
–through the
[General] Internal
Temperature
object
– whenever an increase or decrease greater or equal than
a certain value is detected between two consecutive measurements, no matter
if a periodic sending has been enabled or not. Such value (unsigned) must be
entered here, in terms of tenths of a degree. To avoid having this extra sending
on temperature changes, simply leave the default value (
“0”).
3.2.11
ETHERNET (Z41 PRO AND Z41 COM)
The Ethernet tab permits configuring the Ethernet network interface of Z41 Pro or Z41
COM.
Figure 49
Ethernet (Main Configuration)
The parameters available are: