ZoningBOX 6 / ZoningBOX 4
Technical Support:
27
Temperature Range
[
disabled
/enabled
]: enables the global setpoint
restriction in the groups:
➢
Minimum (Cool Mode)
[
16
…30 ºC
]:
minimum global setpoint allowed to
be sent to the HVAC unit.
➢
Maximum (Heat Mode)
[
16
…30 ºC
]:
maximum global setpoint allowed to
be sent to the HVAC unit.
This function involves the following objects:
“
[Unit x] Setpoint Limits
” (to
activate or deactivate the temperature range restriction at any time) as well as
“
[Unit x] Minimum (Cool Mode)
” and “
[Unit x] Maximum (Heat Mode)
” (to
modify the lower and upper limits dynamically).
Temperature Offset (Increase/Decrease temp. Sent to HVAC Unit)
[
+/-0,0
/ +/-0,5 / +/-1,0 / +/-1,5 / +/-2,0 / +/-2,5
]: sets the value of the increment (in the
heating mode) or the decrement (in the cooling mode) to be applied over the
global setpoint.
The global setpoint temperature is calculated from the value assigned to the following
objects (as stated at the beginning of this section):
“
[Goup n] [Zi] Setpoint Temperature
”: Setpoint temperature of each zone
(T
LSPi
)
“
[Group n] [Zi] Reference Temperature
”: Reference temperature of each
zone (T
REFi
)
“
[Unit x] Return Temperature
”: Return temperature to the unit (T
RET
).
“
[Unit x] Global Temperature Setpoint
”: Setpoint temperature of the climate
control system (T
GSP
).
2.2.6
SCENES
It is possible to define up to six scenes in parameters, whose execution (on the
reception of the corresponding scene number from the bus) will consist in setting a
different HVAC mode and/or a specific fan speed level. It is also possible to define the
zone group (i.e., the HVAC unit) each scene will apply to.