background image

© Zennio Avance y Tecnología S.L. 

Edition 1 

Further information 

www.zennio.com

 

Page 1/2 

 

DALI BOX Interface 64 v3 

Interface for one DALI bus with up to 64 devices and 64 lighting groups 

ZDID64V3 

TECHNICAL DOCUMENTATION 

 

FEATURES 

 

Possibility of controlling up to 64 DALI ballasts and up to 64 lighting 
groups (groups from number 17 to number 64 are only for one DALI 
ballast) 

 

Single Master DALI-2 Controller 

 

Compatibility with emergency lighting and color ballasts (DT8). 

 

Scene sending and saving 

 

Error detection and monitoring 

 

Burn-in, Stand-by and Auto-off functions 

 

Manual control through buttons and status indication through display 

 

1.54” display (128 x 64 pixels) for settings and notifications 

 

External power supply of 110-240 VAC 50/60 Hz 

 

Total data saving on KNX bus failure 

 

Integrated KNX BCU (TP1-256) 

 

Size 67 x 90 x 79 mm (4.5 DIN units) 

 

DIN rail mounting according to IEC 60715 TH35, with fixing clamp 

 

DALI Standard certified 

 

Conformity with  the  CE,  UKCA,  RCM  directives (marks on  the  right 
side) 

  

 

 

1. DALI bus channel 

2. Control buttons 

3. Display 

4.  Programming button 

5. Programming LED 

6.  Power supply indicator LED 

7. External power supply 

8. KNX connector 

Figure 1: DALI BOX Interface 64 v3 

Programming button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe mode. 
 
Programming LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red)  every half  second. During the start-up 
(reset or after KNX bus failure) and if the device is not in safe mode, it emits a red flash. 

GENERAL SPECIFICATIONS 

CONCEPT 

DESCRIPTION 

Type of device 

Electric operation control device 

KNX supply 

Voltage (typical) 

29 VDC SELV 

Voltage range 

21-31 VDC 

Connection type 

Typical TP1 bus connector for 0.8 mm Ø rigid cable 

Maximum 
consumption 

Voltage 

mA 

mW 

29 VDC (typical) 

6,2 

179.8 

24 VDC¹ 

10 

240 

External power 
supply 

Voltage 

110-240 VAC 50/60 Hz PF=0.5 

Maximum consumption 

82 mA @ 110 VAC / 52 mA @ 230 VAC 

Operation temperature 

-5 .. +45 °C 

Storage temperature 

-20 .. +55 °C 

Operation humidity 

5 .. 95% 

Storage humidity 

5 .. 95% 

Complementary characteristics 

Class B 

Protection class / Overvoltage category 

II / III (4200 V) 

Operation type 

Continuous operation 

Device action type 

Type 1 

Electrical stress period 

Long 

Degree of protection 

IP20, clean environment 

Installation 

Independent device to be mounted inside electrical panels with DIN rail (IEC 
60715) 

Minimum clearances 

Not required 

Response on KNX bus failure 

Data saving according to parameterization 

Response on KNX bus restart 

Data recovery according to parameterization 

Operation indicator 

The  programming  LED  indicates  programming  mode  (red).  The  power 
supply  LED  indicates  external  power  (green).  Display  allows  both 
configuring the DALI system and supervising the current status. 

Weight 

195 g 

PCB CTI index 

175 V 

Housing material 

PC FR V0 halogen free 

¹ Maximum consumption in the worst-case scenario (KNX Fan-In model). 

1

 

3

 

2

 

7

 

5

 

4

 

6

 

8

 

Reviews: