DALI BOX Interface 64 v3
Interface for one DALI bus with up to 64 devices and 64 lighting groups
ZDID64V3
TECHNICAL DOCUMENTATION
FEATURES
•
Possibility of controlling up to 64 DALI ballasts and up to 64 lighting
groups (groups from number 17 to number 64 are only for one DALI
ballast)
•
Single Master DALI-2 Controller
•
Compatibility with emergency lighting and color ballasts (DT8).
•
Scene sending and saving
•
Error detection and monitoring
•
Burn-in, Stand-by and Auto-off functions
•
Manual control through buttons and status indication through display
•
1.54” display (128 x 64 pixels) for settings and notifications
•
External power supply of 110-240 VAC 50/60 Hz
•
Total data saving on KNX bus failure
•
Integrated KNX BCU (TP1-256)
•
Size 67 x 90 x 79 mm (4.5 DIN units)
•
DIN rail mounting according to IEC 60715 TH35, with fixing clamp
•
DALI Standard certified
•
Conformity with the CE, UKCA, RCM directives (marks on the right
side)
1. DALI bus channel
2. Control buttons
3. Display
4. Programming button
5. Programming LED
6. Power supply indicator LED
7. External power supply
8. KNX connector
Figure 1: DALI BOX Interface 64 v3
Programming button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe mode.
Programming LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red) every half second. During the start-up
(reset or after KNX bus failure) and if the device is not in safe mode, it emits a red flash.
GENERAL SPECIFICATIONS
CONCEPT
DESCRIPTION
Type of device
Electric operation control device
KNX supply
Voltage (typical)
29 VDC SELV
Voltage range
21-31 VDC
Connection type
Typical TP1 bus connector for 0.8 mm Ø rigid cable
Maximum
consumption
Voltage
mA
mW
29 VDC (typical)
6,2
179.8
24 VDC¹
10
240
External power
supply
Voltage
110-240 VAC 50/60 Hz PF=0.5
Maximum consumption
82 mA @ 110 VAC / 52 mA @ 230 VAC
Operation temperature
-5 .. +45 °C
Storage temperature
-20 .. +55 °C
Operation humidity
5 .. 95%
Storage humidity
5 .. 95%
Complementary characteristics
Class B
Protection class / Overvoltage category
II / III (4200 V)
Operation type
Continuous operation
Device action type
Type 1
Electrical stress period
Long
Degree of protection
IP20, clean environment
Installation
Independent device to be mounted inside electrical panels with DIN rail (IEC
60715)
Minimum clearances
Not required
Response on KNX bus failure
Data saving according to parameterization
Response on KNX bus restart
Data recovery according to parameterization
Operation indicator
The programming LED indicates programming mode (red). The power
supply LED indicates external power (green). Display allows both
configuring the DALI system and supervising the current status.
Weight
195 g
PCB CTI index
175 V
Housing material
PC FR V0 halogen free
¹ Maximum consumption in the worst-case scenario (KNX Fan-In model).
1
3
2
7
5
4
6
8