On the other hand, for connecting the device KLIC-DI to the air-conditioning internal 
unit, the terminal P1/P2 located in the PCB of the AC unit must be connected to 
terminal P1/P2 located in one side of the KLIC-DI (this connector is included as 
accessorize with the device). 

 

If a wired control is included in the installation, the device KLIC-DI can be also 
connected to the terminal P1/P2 of the wired control.  

In order to locate the terminal P1/P2 in the PCB of the wired control, remove the 
casing of the wired control and look for the terminals marked as P/P1 and N/P2. 

CONNECTIONS DIAGRAMS 

KLIC-DI (master, without wired control in the bus):

 

 

 

 

KLIC-DI (master/slave) + wired control (slave/master): 

 

 

Leyend

 

Connection

 

Diagrams

  

A

 

KLIC

 

 

DI

 

B

 

wired

 

control

 

C

 

internal

 

unit

 

P1

‐ 

P2

 

connection

 

bus

 

1

‐ 

2

 

Zennio’s

 

connection

 

terminal

 

*

 

The

 

wired

 

control

 

must

 

work

 

as

 

slave

 

when

 

KLIC

DI

 

is

 

master

 

and

  

vice

 

versa

 

Note: 

The wired remote controller 

BRC1E51A7

 can only work as MASTER. In case this remote controller is installed, 

KLIC-DI should be configured as SLAVE. 

Note:

 The infrared remote controllers 

BRC7*

 and 

BRC4*

 can only work as SLAVE. In case any of these remote 

controllers is installed, KLIC-DI should be configured as MASTER. 

Once the device is powered from the KNX bus, the physical address and the corresponding application program 
KLIC-DI can be downloaded. 

Note

: Each KLIC-DI is 

able to control 

only one

 

internal unit. 

It is not possible to 
connect several internal 
units in series and 
control them with KLIC-
DI. 