Square TMD-Display
http://www.zennio.com
Technical Support:
http://zennioenglish.zendesk.com
79
If Off/Auto is disabled
:
•
“
2:
Min (0% - 50%); Max (51% - 100%)”,
•
“
3:
Min (0% - 33%); Med (34% - 67%); Max (68% - 100%)”.
Representation
: sets the indicator representation. The options are:
“Permanent”, “Temporary”, “Intermittent” and “Progressive”.
Note
:
this parameter will remain hidden unless having selected “Every
indicator is configured separately” in “Indicator representation” (see 2.4).
Object to show/hide indicator
: enables or disables a one-bit object (“
[Disp]
[x] Show/Hide indicator
”) to show or hide the indicator (1 = Show indicator;
0 = Hide indicator).
Note
:
this parameter will remain hidden unless having selected “Enable the
option in every box” in “Object to show/hide the indicator” (see 2.4.1).
[Climate] On/Off + Mode + Status
Figure 67
Display indicator – [Climate] On/Off + Mode + Status.
The icon to be represented depends on the value of three one-bit objects: “
[Disp] [x]
(Climate) On/Off
”, “
[Disp] [x] (Climate) On/Off - Mode
” and “
[Disp] [x] (Climate)
On/Off - Status
”:
“[Disp] [x] (Climate) On/Off” = 0
: no icon is represented.
“[Disp] [x] (Climate) On/Off” = 1 and “[Disp] [x] (Climate) On/Off -
Status” = 0
, it means that the climate system is on but stopped. The icon
represented will depend on the mode selected through “
[Disp] [x]
(Climate) On/Off - Mode
” (1 = Heat or 0 = Cool). The representation type
will be Permanent.
If “[Disp] [x] (Climate) On/Off” = 1 and “[Disp] [x] (Climate) On/Off -
Status” = 1
, it means that the climate is on and running. The icon