Doc Number 801-00015, Version 1.1, Copyright © 2010 Zep Solar, Inc.
PAGE:
11 of 28
ZEP SYSTEM II INSTALLATION MANUAL
After the array layout is determined, verify that
thermal and ground bond allowances are not
exceeded. The Zep array requires a thermal
break at every sixth vertical Module seam as
shown in Figure 4.2C. In order to accomplish a
thermal break, the Interlocks installed at the
thermal break must be only partially secured
as per Section 5.13 below. Interlocks installed
in this fashion do not carry the ground bond so
each portion of the array to either side of the
break requires its own Ground Zep as shown in
Figure 4.2C. If the array exceeds 12 Modules
high (per column) an additional thermal and
ground break is required. One Ground Zep is
required for each array portion segmented
by thermal/ground breaks and a ground bond
jumper must be installed between ground
Zeps as described in Section 5.13 below.
Figure 4.2B
— Cantilever Allowance
Figure 4.2C
— Ground and Thermal Break
NOTE:
Having configured the array, count
the number of Interlocks, Leveling Feet, and
Ground Zeps to create a core components bill
of material.
A = CANTILEVER ALLOWANCE
B = A – 2" (END-FOOT ZONE)
CORRECT
INCORRECT
FOOT LOCATION
END-FOOT ZONE
EDGE OF ARRAY
RAFTERS
END-FOOT ZONE
GROUND & THERMAL BREAK