background image

16  •  Refrigeration

REfRIgERATION

Mechanical Components

EVAPORATOR COIL & EXPANSION VALVE

The evaporator coil is located in the bottom of the case under the deck pans. The 

thermostatic expansion valve (TXV) is typically located at the end of the evaporator 

coil. The TXV is not preset, and superheat should be adjusted to 6-8°F. Contact 

Zero Zone for superheat setting if using high-glide refrigerants.

To adjust the TXV, remove the far right deck pan (

See Figure 30

). Remove the cap 

from the bottom of the TXV. When looking at the valve stem end, turn the valve 

stem counterclockwise to decrease superheat. Turn the valve stem clockwise to 

increase superheat. Measure the suction line temperature at the TXV sensing bulb 

and compare it to the suction temperature corresponding to the saturated pressure. 

Make sure that line pressure drop is taken into account. Turn the valve stem only 

1/4 turn at a time and allow sufficient time (20 to 30 minutes) for the TXV to settle 

before making further adjustments. After the superheat has been adjusted, wipe the 

valve stem cap dry and screw it back on.

EVAPORATOR FANS

Air is circulated through the display case by fans, which are located below the deck pans in the bottom of the case (

See Figure 31

). Air is drawn 

through the front return air grill and discharged out of the honeycomb at the top. The fan motors must be operating at all times. Fan motors 

should be replaced with motors having the same characteristics including type, physical size, lubricant temperature range, wattage, and RPM. 

Fan blades should be replaced with OEM parts or have the same fan pitch as the OEM fan blade.

CAUTION! 

 

DISCONNECT POWER TO THE CASE BEFORE SERVICINg ELECTRICAL 

COMPONENTS TO AVOID PERSONAL INJuRY AND DAMAgE TO THE uNIT.

1.  Disconnect power to the fan.
2.  Remove the fan blade nut and fan blade.
3.  Remove the mounting bolts and remove the fan assembly from the fan housing.
4.  Remove the fan motor mounting screws from the back of the fan motor.
5.  Replace the fan, and reverse steps 1-3 to install the cover. Restore case power.

Refrigerant Piping

Unless otherwise specified, the liquid and suction connections terminate inside the case under the coil 

cover. Refrigerant piping may enter the case through the left rear back panel or the left rear top panel of 

the case. Other exit options are available. The copper pipe should not touch or rub on the edges of the 

sheet metal. Correct refrigeration line sizing and industry standard installation practices are essential for 

proper system operation (

See Figure 32 on page 17

).

After connections have been made, the refrigeration access holes or penetrations in the case must be 

sealed completely with an aerosol-dispensed urethane insulation or equivalent (example: great Stuff).

After all of the refrigeration piping and system components have been assembled, the entire system must 

be pressurized and checked for leaks. When the system is leak free, evacuate with a deep vacuum pump. 

Triple evacuation should be done to 500 microns or less, and nitrogen sweep is recommended. After the 

system has been thoroughly evacuated of all moisture and non-condensable gas, charge the system with 

the specified refrigerant.

REfRIgERATION

 FIGURE 30: Expansion Valve and Schrader Valve

 FIGURE 31: Fans and  

Case-to-Case Piping

Summary of Contents for Reveal Merchandiser ORMC75-MX

Page 1: ...ZERO ZONE REVEAL MERCHANDISER OPEN MULTI DECKS With ChillBrite LED Lighting INSTALLATION OPERATION MANUAL COMPLIANT 66 0057 REV E Aug 2021...

Page 2: ...Night Curtains 14 Under Shelf Lights 14 Canopy Lights 15 Shelves Stocking Product 15 REFRIGERATION 16 Mechanical Components 16 Evaporator Coil Expansion Valve 16 Evaporator Fans 16 Refrigerant Piping...

Page 3: ...all not be covered by this warranty Extended Warranties In addition to the standard limited warranty for further consideration the Seller will extend to the original purchaser prior to shipment a limi...

Page 4: ...questions or problems arise call Zero Zone at 800 247 4496 Any change to a Zero Zone product made during the installation start up or at any other time must be submitted in writing to Zero Zone for ap...

Page 5: ...Refrigerators and Freezers ANSI Approved equipment certified by NSF NSF 51 Food Equipment Materials ANSI Approved equipment certified by NSF UL 471 Commercial Refrigerators and Freezers ANSI Approved...

Page 6: ...the right end and the second case in the lineup will be labeled on the left end The numbers on each end to be joined will match See Figure 1 The first case in a lineup with the right side labeled x 1...

Page 7: ...instructions CASE MODEL INSTRUCTIONS 4ORMC Forks must extend 20 to 24 under the case from either end 6ORMC Forks must extend 26 to 30 under the case from either end 8ORMC Forks must extend 39 to 43 u...

Page 8: ...not extend beyond the front case bases or they will interfere with installing trim The shims should be oriented to sit under the front and rear bends of each base Tape all shims in place See Figure 7...

Page 9: ...peration 7 Installation Operation Figure 8 Reveal Merchandiser Base Locations 4ORMC 6ORMC 8ORMC 12ORMC Drawings are top views with bases shown under the case Case length does not include end panels 1...

Page 10: ...e setting the next case in the lineup Case caulking instructions and caulk are shipped with every case See Figure 10 on page 9 Move the next case into position and bolt it to the first case using the...

Page 11: ...e to ensure a tight seal 3 Repeat this process between each case in the lineup SURFACES TO BE CAULKED MUST BE CLEAN DRY AND FREE OF FROST ABOVE 40 F Note NSF sealant must be applied with no gaps to se...

Page 12: ...eed to loosen the canopy screws if canopies are not within 3 8 On cases with stainless steel canopies the splice is shipped loose Fit it over both canopies and screw into place Hand Rail Splice Some c...

Page 13: ...s of drain pipe should be installed through the bases See Figure 17 There is no room in front of the base for the drain pipe because the kickplate installs directly to the front of the bases Install t...

Page 14: ...If a continuous bumper is used only the bumper support and snap track will be installed The continuous bumper may need to be trimmed before snapping it onto the snap track Figure 18 Kickplate Installa...

Page 15: ...Install Mirror Support into the Shelf Standards Install into second and third slots from the top Figure 21 Shelf Standard Slots for Air Deflector MIRROR HEIGHT SLOT FOR AIR DEFLECTOR 8 Tall 6th Slot...

Page 16: ...st it until you hear a click as the brackets engage See Figure 24 Once installed the night curtain can be pulled down See Figure 25 Under Shelf Lights 1 Position the under shelf light on the bottom of...

Page 17: ...rack Note Do not place product on the return air grille or past the load limit line Do not exceed shelf load capacity See Figure 28 Do not stand on the case when stocking or adjusting shelves SHELF T...

Page 18: ...hould be replaced with OEM parts or have the same fan pitch as the OEM fan blade CAUTION DISCONNECT POWER TO THE CASE BEFORE SERVICING ELECTRICAL COMPONENTS TO AVOID PERSONAL INJURY AND DAMAGE TO THE...

Page 19: ...valent feet 90 F Liquid 2 F Pressure Drop Up to 150 equivalent feet 90 F Liquid 2 F Pressure Drop Up to 150 equivalent feet 90 F Liquid 2 F Pressure Drop It may be necessary to make adjustments to com...

Page 20: ...rost may cause premature defrost termination Case Thermometer The cases are shipped with two thermometers One thermometer is factory mounted in the center ceiling pocket cover to sense the discharge a...

Page 21: ...case wiring See Figure 37 Terminal blocks are provided for supplying power for fans and lights A ground connection can also be made inside the electrical enclosure Optional top electrical will be loca...

Page 22: ...a mild detergent and warm water or a mild sanitizer 6 If the case is equipped with a condensate pan and pump the drain should be blocked before washing coils Water can be removed with a shop vacuum 7...

Page 23: ...cal Resources page at WWW ZERO ZONE COM or contact the Zero Zone Service Department at 800 247 4496 All specifications subject to change without notice 66 0057 REV E ZERO ZONE INC 800 247 4496 ZERO ZO...

Reviews: