background image

Refrigeration  •  17

REfRIgERATION

From

To

Liquid Line

From

To

Liquid Line

From

To

Liquid Line

From

To

Liquid Line

5,280

30,720

3/8

5,280

21,010

3/8

5,280

16,790

3/8

5,280

14,310

3/8

30,730

72,750

1/2

21,020

49,900

1/2

16,800

39,960

1/2

14,320

34,110

1/2

72,760 136,380

5/8

49,910

93,740

5/8

39,970

75,160

5/8

34,120

64,210

5/8

136,390 226,300

3/4

93,750 155,790

3/4

75,170 125,030

3/4

64,220 106,890

3/4

155,800 246,590

7/8

125,040 198,070

7/8

106,900 169,440

7/8

From

To

Horizontal

From

To

Horizontal

From

To

Horizontal

From

To

Horizontal

5,280

8,350

1/2

5,280

5,730

1/2

---

---

---

---

---

---

8,360

15,640

5/8

5,740

10,760

5/8

5,280

8,630

5/8

5,280

7,380

5/8

15,650

25,950

3/4

10,770

17,880

3/4

8,640

14,360

3/4

7,390

12,280

3/4

25,960

41,010

7/8

17,890

28,290

7/8

14,370

22,740

7/8

12,290

19,460

7/8

41,020

82,770

1-1/8

28,300

57,220

1-1/8

22,750

46,030

1-1/8

19,470

39,430

1-1/8

82,780 143,860

1-3/8

57,230

95,580

1-3/8

46,040

80,190

1-3/8

39,440

68,720

1-3/8

143,870 226,880

1-5/8

95,590 157,230

1-5/8

80,200 126,700

1-5/8

68,730 108,640

1-5/8

157,240 325,130

2-1/8

126,710 262,250

2-1/8

108,650 225,030

2-1/8

From

To

Vertical

5,280

6,590

5/8

6,600

10,500

3/4

10,510

21,300

7/8

21,310

37,300

1-1/8

37,310

59,100

1-3/8

59,110 121,880

1-5/8

121,890 215,800

2-1/8

90°F Liquid, 2°F Pressure Drop

Up to 50 equivalent feet

For 1°F pressure drop, multiply rated Btuh by 1.44 before using the Suction Horizontal Line Sizing Table.

For 1°F pressure drop, multiply rated Btuh by 1.45 before using the Liquid Line Sizing Table.

Suction Vertical Riser Sizing

Up to 100 equivalent feet

Up to 50 equivalent feet

90°F Liquid, 2°F Pressure Drop

Up to 100 equivalent feet

Up to 200 equivalent feet

90°F Liquid, 2°F Pressure Drop

Liquid Line Sizing

Suction Horizontal Line Sizing

90°F Liquid, 2°F Pressure Drop

Up to 200 equivalent feet

90°F Liquid, 2°F Pressure Drop

Up to 150 equivalent feet

90°F Liquid, 2°F Pressure Drop

Up to 150 equivalent feet

90°F Liquid, 2°F Pressure Drop

It may be necessary to make adjustments to compensate for special situations 

which cause the actual Btuh to differ from the rated Btuh of the cases. 
All liquid line and suction line sizes are inches, refrigeration O.D.
Subject to change without notice.

70°F Minimum Liquid Temperature, using 0.35 PSI Per 100 Feet (per 2006 ASHRAE Handbook - Refrigeration)

For rated Btuh:

Maximum Allowable Riser Size For Adequate Oil Return*

R-404 Line Sizing Tables for Zero Zone OVMC Multideck (+26°F Evaporator Temperature)

For rated Btuh:

For rated Btuh:

For rated Btuh:

For rated Btuh:

For rated Btuh:

For rated Btuh:

For rated Btuh:

For rated Btuh:

90°F Liquid, 2°F Pressure Drop

Liquid Correction Factors for Suction Vertical Riser Sizing Table - Use Minimum Liquid Temperature

Multiply rated Btuh by liquid correction factor before using the Suction Vertical Riser Sizing Table

40°F

50°F

60°F

70°F

80°F

90°F

100°F

0.85

0.89

0.94

1.00

1.07

1.15

1.24

Minimum Liquid Temperature:

Liquid Correction Factor:

40°F

50°F

60°F

70°F

80°F

90°F

100°F

120°F

0.74

0.78

0.82

0.87

0.93

1.00

1.08

1.32

1.19

Liquid Correction Factors for Suction Horizontal Line Sizing Table - Use Maximum Liquid Temperature

For max imum liquid temperatures other than 90°F, multiply  rated Btuh by  liquid correction factor before using the Suction Horizontal Line Sizing Table

Max imum Liquid Temperature:

110°F

Liquid Correction Factor:

40°F

50°F

60°F

70°F

80°F

90°F

100°F

120°F

0.98

0.97

0.96

0.97

0.98

1.00

1.04

1.17

Liquid Correction Factors for Liquid Line Sizing Table - Use Maximum Liquid Temperature

For maximum liquid temperatures other than 90°F, multiply rated Btuh by liquid correction factor before using the Liquid Line Sizing Table

Max imum Liquid Temperature:

110°F

Liquid Correction Factor:

1.09

 FIGURE 32: R-404A Line Sizing Tables for Zero Zone ORMC Multi-Deck (26°F Evaporator Temperature)

Summary of Contents for Reveal Merchandiser ORMC75-MX

Page 1: ...ZERO ZONE REVEAL MERCHANDISER OPEN MULTI DECKS With ChillBrite LED Lighting INSTALLATION OPERATION MANUAL COMPLIANT 66 0057 REV E Aug 2021...

Page 2: ...Night Curtains 14 Under Shelf Lights 14 Canopy Lights 15 Shelves Stocking Product 15 REFRIGERATION 16 Mechanical Components 16 Evaporator Coil Expansion Valve 16 Evaporator Fans 16 Refrigerant Piping...

Page 3: ...all not be covered by this warranty Extended Warranties In addition to the standard limited warranty for further consideration the Seller will extend to the original purchaser prior to shipment a limi...

Page 4: ...questions or problems arise call Zero Zone at 800 247 4496 Any change to a Zero Zone product made during the installation start up or at any other time must be submitted in writing to Zero Zone for ap...

Page 5: ...Refrigerators and Freezers ANSI Approved equipment certified by NSF NSF 51 Food Equipment Materials ANSI Approved equipment certified by NSF UL 471 Commercial Refrigerators and Freezers ANSI Approved...

Page 6: ...the right end and the second case in the lineup will be labeled on the left end The numbers on each end to be joined will match See Figure 1 The first case in a lineup with the right side labeled x 1...

Page 7: ...instructions CASE MODEL INSTRUCTIONS 4ORMC Forks must extend 20 to 24 under the case from either end 6ORMC Forks must extend 26 to 30 under the case from either end 8ORMC Forks must extend 39 to 43 u...

Page 8: ...not extend beyond the front case bases or they will interfere with installing trim The shims should be oriented to sit under the front and rear bends of each base Tape all shims in place See Figure 7...

Page 9: ...peration 7 Installation Operation Figure 8 Reveal Merchandiser Base Locations 4ORMC 6ORMC 8ORMC 12ORMC Drawings are top views with bases shown under the case Case length does not include end panels 1...

Page 10: ...e setting the next case in the lineup Case caulking instructions and caulk are shipped with every case See Figure 10 on page 9 Move the next case into position and bolt it to the first case using the...

Page 11: ...e to ensure a tight seal 3 Repeat this process between each case in the lineup SURFACES TO BE CAULKED MUST BE CLEAN DRY AND FREE OF FROST ABOVE 40 F Note NSF sealant must be applied with no gaps to se...

Page 12: ...eed to loosen the canopy screws if canopies are not within 3 8 On cases with stainless steel canopies the splice is shipped loose Fit it over both canopies and screw into place Hand Rail Splice Some c...

Page 13: ...s of drain pipe should be installed through the bases See Figure 17 There is no room in front of the base for the drain pipe because the kickplate installs directly to the front of the bases Install t...

Page 14: ...If a continuous bumper is used only the bumper support and snap track will be installed The continuous bumper may need to be trimmed before snapping it onto the snap track Figure 18 Kickplate Installa...

Page 15: ...Install Mirror Support into the Shelf Standards Install into second and third slots from the top Figure 21 Shelf Standard Slots for Air Deflector MIRROR HEIGHT SLOT FOR AIR DEFLECTOR 8 Tall 6th Slot...

Page 16: ...st it until you hear a click as the brackets engage See Figure 24 Once installed the night curtain can be pulled down See Figure 25 Under Shelf Lights 1 Position the under shelf light on the bottom of...

Page 17: ...rack Note Do not place product on the return air grille or past the load limit line Do not exceed shelf load capacity See Figure 28 Do not stand on the case when stocking or adjusting shelves SHELF T...

Page 18: ...hould be replaced with OEM parts or have the same fan pitch as the OEM fan blade CAUTION DISCONNECT POWER TO THE CASE BEFORE SERVICING ELECTRICAL COMPONENTS TO AVOID PERSONAL INJURY AND DAMAGE TO THE...

Page 19: ...valent feet 90 F Liquid 2 F Pressure Drop Up to 150 equivalent feet 90 F Liquid 2 F Pressure Drop Up to 150 equivalent feet 90 F Liquid 2 F Pressure Drop It may be necessary to make adjustments to com...

Page 20: ...rost may cause premature defrost termination Case Thermometer The cases are shipped with two thermometers One thermometer is factory mounted in the center ceiling pocket cover to sense the discharge a...

Page 21: ...case wiring See Figure 37 Terminal blocks are provided for supplying power for fans and lights A ground connection can also be made inside the electrical enclosure Optional top electrical will be loca...

Page 22: ...a mild detergent and warm water or a mild sanitizer 6 If the case is equipped with a condensate pan and pump the drain should be blocked before washing coils Water can be removed with a shop vacuum 7...

Page 23: ...cal Resources page at WWW ZERO ZONE COM or contact the Zero Zone Service Department at 800 247 4496 All specifications subject to change without notice 66 0057 REV E ZERO ZONE INC 800 247 4496 ZERO ZO...

Reviews: