18  •  Refrigeration

REfRIgERATION

glycol cases typically have a balance valve located in the outlet line inside of the case. If a stop solenoid is provided, it will also be located in 

the outlet line. Schrader valves are provided inside the case on the right-hand side of the coil for venting and draining the system.

Operation Set Points

Refer to the case spec sheet for btu/h requirements and electrical requirements. Operate the case at the proper settings to maintain product 

temperature of 41°F or below, per food safety regulations (

See Figure 33

). 

Note: Set points based on flat shelves. Alternate shelving—

such as angled or tiered shelving, peg hooks, or produce inserts—may require lower operating temperatures.

Off-Cycle Defrost

See Figure 34

 for off-cycle defrost settings. During off-cycle defrost, refrigerant is stopped either by stopping the compressor or by closing the 

liquid line solenoid valve and allowing the compressor to pump down. The fans and lights remain on during off-cycle defrost.

If temperature termination is selected, set the termination temperature at 45°F for discharge air and coil temperature. 

Note: Stocking or 

shopping during off-cycle defrost may cause premature defrost termination.

Case Thermometer

The cases are shipped with two thermometers. One thermometer is factory-mounted in the center ceiling pocket cover to sense the discharge 

air stream. The second thermometer is shipped loose and should be installed in the warmest product location as required by NSF. Specific field 

installation instructions are packaged with the thermometer that is shipped loose.

 FIGURE 34: Defrost Settings

SETTING

MEAT

DAIRY/DELI/PRODUCE

BEVERAGE

Defrost Type

Off-Cycle

Off-Cycle

Off-Cycle

Frequency

4 Per Day

4 Per Day

4 Per Day

Duration

36 Minutes

30 Minutes

30 Minutes

 FIGURE 33: Case Temperature Internal Control Options (R-404A)

SETTING

MEAT

DAIRY/DELI/PRODUCE

BEVERAGE

Evaporator Temperature

22°F

26°F

28°F

Condensing Unit Cut-In

62 psig

67 psig

71 psig

Condensing Unit Cut-Out

54 psig

59 psig

62 psig

Return Air Temperature Cut-In

44°F

48°F

50°F

Return Air Temperature Cut-Out

40°F

44°F

46°F

Discharge Air Temperature Cut-In

31°F

35°F

37°F

Discharge Air Temperature Cut-Out

27°F

31°F

33°F

Superheat Setting

6-8°F

6-8°F

6-8°F

Note: For high-glide refrigerants, use dew point for unit sizing. Adjust evaporator pressure as needed to maintain 

discharge air temperatures. To receive the full benefit of high-glide refrigerant properties, the superheat may need to 

be lowered to 4-6°F. Contact Zero Zone with questions.

Summary of Contents for Reveal Merchandiser ORMC75-MX

Page 1: ...ZERO ZONE REVEAL MERCHANDISER OPEN MULTI DECKS With ChillBrite LED Lighting INSTALLATION OPERATION MANUAL COMPLIANT 66 0057 REV E Aug 2021...

Page 2: ...Night Curtains 14 Under Shelf Lights 14 Canopy Lights 15 Shelves Stocking Product 15 REFRIGERATION 16 Mechanical Components 16 Evaporator Coil Expansion Valve 16 Evaporator Fans 16 Refrigerant Piping...

Page 3: ...all not be covered by this warranty Extended Warranties In addition to the standard limited warranty for further consideration the Seller will extend to the original purchaser prior to shipment a limi...

Page 4: ...questions or problems arise call Zero Zone at 800 247 4496 Any change to a Zero Zone product made during the installation start up or at any other time must be submitted in writing to Zero Zone for ap...

Page 5: ...Refrigerators and Freezers ANSI Approved equipment certified by NSF NSF 51 Food Equipment Materials ANSI Approved equipment certified by NSF UL 471 Commercial Refrigerators and Freezers ANSI Approved...

Page 6: ...the right end and the second case in the lineup will be labeled on the left end The numbers on each end to be joined will match See Figure 1 The first case in a lineup with the right side labeled x 1...

Page 7: ...instructions CASE MODEL INSTRUCTIONS 4ORMC Forks must extend 20 to 24 under the case from either end 6ORMC Forks must extend 26 to 30 under the case from either end 8ORMC Forks must extend 39 to 43 u...

Page 8: ...not extend beyond the front case bases or they will interfere with installing trim The shims should be oriented to sit under the front and rear bends of each base Tape all shims in place See Figure 7...

Page 9: ...peration 7 Installation Operation Figure 8 Reveal Merchandiser Base Locations 4ORMC 6ORMC 8ORMC 12ORMC Drawings are top views with bases shown under the case Case length does not include end panels 1...

Page 10: ...e setting the next case in the lineup Case caulking instructions and caulk are shipped with every case See Figure 10 on page 9 Move the next case into position and bolt it to the first case using the...

Page 11: ...e to ensure a tight seal 3 Repeat this process between each case in the lineup SURFACES TO BE CAULKED MUST BE CLEAN DRY AND FREE OF FROST ABOVE 40 F Note NSF sealant must be applied with no gaps to se...

Page 12: ...eed to loosen the canopy screws if canopies are not within 3 8 On cases with stainless steel canopies the splice is shipped loose Fit it over both canopies and screw into place Hand Rail Splice Some c...

Page 13: ...s of drain pipe should be installed through the bases See Figure 17 There is no room in front of the base for the drain pipe because the kickplate installs directly to the front of the bases Install t...

Page 14: ...If a continuous bumper is used only the bumper support and snap track will be installed The continuous bumper may need to be trimmed before snapping it onto the snap track Figure 18 Kickplate Installa...

Page 15: ...Install Mirror Support into the Shelf Standards Install into second and third slots from the top Figure 21 Shelf Standard Slots for Air Deflector MIRROR HEIGHT SLOT FOR AIR DEFLECTOR 8 Tall 6th Slot...

Page 16: ...st it until you hear a click as the brackets engage See Figure 24 Once installed the night curtain can be pulled down See Figure 25 Under Shelf Lights 1 Position the under shelf light on the bottom of...

Page 17: ...rack Note Do not place product on the return air grille or past the load limit line Do not exceed shelf load capacity See Figure 28 Do not stand on the case when stocking or adjusting shelves SHELF T...

Page 18: ...hould be replaced with OEM parts or have the same fan pitch as the OEM fan blade CAUTION DISCONNECT POWER TO THE CASE BEFORE SERVICING ELECTRICAL COMPONENTS TO AVOID PERSONAL INJURY AND DAMAGE TO THE...

Page 19: ...valent feet 90 F Liquid 2 F Pressure Drop Up to 150 equivalent feet 90 F Liquid 2 F Pressure Drop Up to 150 equivalent feet 90 F Liquid 2 F Pressure Drop It may be necessary to make adjustments to com...

Page 20: ...rost may cause premature defrost termination Case Thermometer The cases are shipped with two thermometers One thermometer is factory mounted in the center ceiling pocket cover to sense the discharge a...

Page 21: ...case wiring See Figure 37 Terminal blocks are provided for supplying power for fans and lights A ground connection can also be made inside the electrical enclosure Optional top electrical will be loca...

Page 22: ...a mild detergent and warm water or a mild sanitizer 6 If the case is equipped with a condensate pan and pump the drain should be blocked before washing coils Water can be removed with a shop vacuum 7...

Page 23: ...cal Resources page at WWW ZERO ZONE COM or contact the Zero Zone Service Department at 800 247 4496 All specifications subject to change without notice 66 0057 REV E ZERO ZONE INC 800 247 4496 ZERO ZO...

Reviews: