Chilli Pro 12
The Chilli Pro 12 has the following knockouts:
Top 2 x Ø50.0mm,1 x Ø32.0mm
Bottom 2 x Ø25.5mm
Appropriate cable glands should be fitted to the knockout holes provided to protect the mains cables from damage.
The channel (load) cables are connected to the terminal strips located on the top right of the unit. The outputs will
accept a maximum 6mm
2
cable. Based on the variant you have; the channel loads will be protected by either MCB or
RCBO.
Phase 1 (brown*): Channels 1, 4, 7, 10
Phase 2 (black*): Channels 2, 5, 8, 11
Phase 3 (grey*): Channels 3, 6, 9, 12
*IEC Standard wiring colour codes
There is a dedicated terminal for the live and neutral of each output
circuit. A shared Earth bus bar is mounted on the chassis of the
dimmer.
Chilli Pro 24
The Chilli Pro 24 has the following knockouts:
Top 4 x Ø50.0mm, 2 x Ø32.0mm
Bottom 2 x Ø25.5mm
Appropriate cable glands should be fitted to the knockout holes provided to protect the mains cables from damage.
The channel (load) cables are connected to the terminal strips. Channels 1 – 12 are located on the left hand side of
the unit, and Channels 13 – 24 are located on the right hand side of the unit. The outputs will accept a maximum 6mm
2
cable. Based on the variant you have; the channel loads will be protected by either MCB or RCBO.
Phase 1 (brown*): Channels 1, 4, 7, 10, 13, 16, 19, 22
Phase 2 (black*): Channels 2, 5, 8, 11, 14, 17, 20, 23
Phase 3 (grey*): Channels 3, 6, 9, 12, 15, 18, 21, 24
*IEC Standard wiring colour codes