Doc: GLT-211-7-3
Iss: 2.0
Date 03/08/2016
Addressing the System.
The ID2 divides the loop addresses into zones and Ids. The panel translates the address into a zone
and ID. Each zone starts with ID1, in order to simplify the addressing.
To assist with setting the dip switches, there is a free app available for download on the APP Store
for iOS, or Google Play for Android
Once all the installation has been checked for any cable faults, and all the devices have been
addressed and fitted, connect the loop or radial circuits and turn the panel on.
CONNECTING MAINS POWER
CONNECTING THE BATTERIES
The panel should be connected to 220-240V
AC by a 3A rated spur to the fuse box with
1mm
2
to 2.5mm
2
3-core cable.
Nothing else should be connected to this
supply. The cable should be fire resistant.
Although there are many sizes of suitable battery,
the sizes we usually recommend for the ID2 are 12V
7Ah,
The two batteries are wired in series to give 24
Volts.