PREMIER EVACS 1-16 INSTRUCTION MANUAL: 2-ZONE NETWORKED VOICE ALARM PANEL
Document no: GLT-237-7-1
PAGE 13
Issue: 1.5
Date: 02/04/2014
Networking the panel
The EVACS 1-16 allows up to 16 panels to be connected over RS485 network interface, with each panel, or module,
acting as a 2-channel zone. Individual panels or zones can then be controlled by the master panel.
The network address can be set using switches 1-4 of the DIP switch located on the amplifier board. The master
panel or a panel which is not part of a network must be set an address of 1.
Address
SW1
SW2
SW3
SW4
1 (Master, or stand-alone panel)
OFF
OFF
OFF
OFF
2
OFF
OFF
OFF
ON
3
OFF
OFF
ON
OFF
4
OFF
OFF
ON
ON
5
OFF
ON
OFF
OFF
6
OFF
ON
OFF
ON
7
OFF
ON
ON
OFF
8
OFF
ON
ON
ON
9
ON
OFF
OFF
OFF
10
ON
OFF
OFF
ON
11
ON
OFF
ON
OFF
12
ON
OFF
ON
ON
13
ON
ON
OFF
OFF
14
ON
ON
OFF
ON
15
ON
ON
ON
OFF
16
ON
ON
ON
ON
The network connection terminals are labelled COMA, 0V and COMB. Each should be wired to the corresponding
terminal of the next panel on the network. The panels themselves do not need to be wired in any particular order
with regard to the address used.