PREMIER EVACS 1-16 INSTRUCTION MANUAL: 2-ZONE NETWORKED VOICE ALARM PANEL
Document no: GLT-237-7-1
PAGE 14
Issue: 1.5
Date: 02/04/2014
The master panel must be configured with the number of zones on the network (that is, the number of EVACS 1-16
panels, including the master panel). This is done with the EVACS 1-16 configuration software via the USB link.
To set the number of zones, connect the PC to the EVACS 1-16 panel via a suitable USB cable and run the EVACS 1-16
configuration software. Note that the panel must be powered on.
In the configuration software, select settings, select the desired number of zones and click OK.
The panel should now be configured with the correct number of zones.
SWITCH ON
OFF
Notes
SW5
RESERVED
RESERVED
RESERVED – SET TO ‘OFF’
SW6
RESERVED
RESERVED
RESERVED – SET TO ‘OFF’
SW7
Master Alarm
Local Alarm
SW8
Local microphone
Broadcast microphone