PREMIER EVACS 1-16 INSTRUCTION MANUAL: 2-ZONE NETWORKED VOICE ALARM PANEL
Document no: GLT-237-7-1
PAGE 15
Issue: 1.5
Date: 02/04/2014
Connecting the EVACS 1-16 to an analogue addressable panel
The EVACS 1-16 allows connection to an analogue addressable panel via the loop interface. In a network of multiple
EVACS 1-16 panels, the CIE must be connected to the master panel.
The EVACS 1-16 utilises the Fyreye MKII protocol and must be connected to a panel running the MKII software.
The device address of the EVACS 1-16 is set by the 8-way dip switch located on the display PCB,
the address is set in binary notation, with switch 1 being the most significant bit (MSB) and
switch 8 being the least significant bit (LSB). Refer to the table on the left for a list of each
switch value, or the tables on the following pages for a quick reference of all addresses. Note
that address 0 is reserved and should not be used.
Switch Address
value
SW1
+128
SW2
+64
SW3
+32
SW4
+16
SW5
+8
SW6
+4
SW7
+2
SW8
+1