PREMIER EVACS 1-16 INSTRUCTION MANUAL: 2-ZONE NETWORKED VOICE ALARM PANEL
Document no: GLT-237-7-1
PAGE 17
Issue: 1.5
Date: 02/04/2014
Configuring the Voice Messages, and Trigger Inputs
The EVACS 1-16 panel can be configured using the EVACS software. To configure the software the panel must be
powered on and plugged into the PC running the software using a suitable USB connector.
For the EVACS 1-16 the drop-down list box in the centre of the dialogue should be set to EVACS 1-16.
For networked EVACS 1-16 panels, most settings are only available to the panel configured as master.
On the Premier EVACS 1-16, alert and evacuation messages can be uploaded from a PC running the configuration
software. The messages cannot be recorded direct to the panel due to the microphones limited dynamic range,
which would result in poor quality pre-recorded messages.
Any suitable Audio file can be uploaded. The file format is *.wav format, 16-bit, 1 channel (mono), uncompressed
16,000 samples/sec (256kbps) with a maximum length of 55 seconds
A custom message can be recorded on a PC or in a sound studio if the best sound clarity is required. Alternatively,
you can use one of the sample messages provided with the PC Configuration Software.