An example configuration file might look like this:
[Alert]
Message=C:\Program Files\Zeta Alarms\Messages\AlertFem.wav
Tone=7
[Evac]
Message=C:\Program Files\Zeta Alarms\Messages\EvacMale.wav
Tone=1
[Mic]
Signon=C:\Program Files\Zeta Alarms\Page\Page1.wav
Signoff= C:\Program Files\Zeta Alarms\Page\Page2.wav
[Comms]
Port=COM3
[Alert] section: Specifies the message and tone to be played for zones in the ALERT status
[Evac] section: Specifies the message and tone to be played for zones in the EVACUATE status
[Mic] section: Specifies the audio files to be played for the sign-on and sign-off for the microphone
[Comms] section: specifies the communications parameters. The communications port the EVACS 1-16 panel is
detected on should be displayed in the lower left of the EVACS software main screen.
List of available tones
Tone Type
Primary (f1) /
start frequency
(Hz)
Secondary (f2) /
end frequency
(Hz)
Sweep
duration
(mS)
On Period
or f1 time
(mS)
Off period
or f2 time
(mS)
1
Alternating
800
970
--
250
250
2
Sweep
800
970
140
--
--
3
Sweep
800
970
1000
--
--
4
Intermittent
970
--
--
250
1000
5
Continuous
970
--
--
--
--
6
Sweep
800
970
20
--
--
7
Intermittent
970
--
--
500
500
8
Alternating
554
440
--
100
400
9
Sweep
500
1200
300
--
--
10
Intermittent
420
--
--
600
600
11
Sweep
2400
2850
140
--
--
12
Continuous
660
--
--
--
--
13
Alternating
554
440
--
500
500
14
Intermittent
2850
--
--
500
500
15
Sweep
1200
500
1000
--
--
16
Continuous
2850
--
--
--
--
Note: All times are in milliseconds (mS), where 1000mS = 1 second.