PREMIER EVACS 1-16 INSTRUCTION MANUAL: 2-ZONE NETWORKED VOICE ALARM PANEL
Document no: GLT-237-7-1
PAGE 33
Issue: 1.5
Date: 02/04/2014
Specifications
Electrical Specifications
ELECTRICAL DESCRIPTION
VALUE
MAINS VOLTAGE
100-120V AC / 200-240V AC ± 10% @ 50/60Hz
MAINS CURRENT
8.0A MAX
SYSTEM VOLTAGE
29.5V NOMINAL ± 10%
QUIESCIENT CURRENT DRAW
60mA
ALARM CONDITION CURRENT DRAW
500mA
MAX SYSTEM CURRENT DRAW
7.8A
MAX SYSTEM POWER DRAW
255W
BATTERY SPECIFICATION
24V DC (2X 7.2AH, 12V SLA BATTERY)
CHARGER SIZE
24V, 7.2Ah – 17Ah
SPEAKER LINE VOLTAGE
100V NOMINAL
MINIMUM SPEAKER IMPEDANCE
600Ω @ 1KHz
MINIMUM RESISTIVE LOAD
1260Ω
MAXIMUM CAPACITIVE LOAD
110nF
OUTPUT PER CHANNEL
MAX 30W
TOTAL OUTPUT
MAX 60W
ALARM OUTPUT
2 x 500mA 28V DC
FAULT OUTPUT
1X RELAY SELV NORMALLY ENERGISED
PANEL INPUTS
1X ALERT
1X EVACUATE
DESCRIPTION
VALUE
DIMENSIONS (h x w x d)
475.5 x 400 x 143mm
WEIGHT
7.1Kg
TOP CABLE ENTRIES
28
BOTTOM CABLE ENTRIES
6
FUSE NO
DESCRIPTION
RATING
FS1
AMPLIFIER PROTECTION FUSE (CH1)
3.15A time delay 5x20mm ceramic
FS2
AMPLIFIER PROTECTION FUSE (CH2)
3.15A time delay 5x20mm ceramic
--
SOUNDER OUTPUT PROTECTION (S1)
500mA self-resetting PTC fuse
--
SOUNDER OUTPUT PROTECTION (S1)
500mA self-resetting PTC fuse
--
AUX POWER PROTECTION
500mA self-resetting PTC fuse