PREMIER EVACS 1-16 INSTRUCTION MANUAL: 2-ZONE NETWORKED VOICE ALARM PANEL
Document no: GLT-237-7-1
PAGE 5
Issue: 1.5
Date: 02/04/2014
Safety information & use of this manual
WARNING:
Read this section completely before operating this equipment.
Installation information
THIS VOICE ALARM CONTROL & INDICATING EQUIPMENT (VACIE) IS CLASS-1 EQUIPMENT AND MUST BE EARTHED.
This equipment must be installed and maintained by a qualified and technically experienced person.
This VACIE must be wired to a fused spur rated at 5A. It must
NOT
be connected via a removable plug, or be
connected through an RCD device.
Prior to commencing installation of the control panel, ensure that adequate precautions are taken to prevent damage to the
sensitive electronic components on the display board and the control board due to electrostatic discharge. If anti-static
equipment (such as an anti-static wrist strap) is not available, you should discharge any static electricity you may have
accumulated by touching a convenient earthed object such as an unpainted copper radiator pipe. You should repeat the process
at regular intervals during the installation process, especially if you are required to walk over carpets.
The panel must be located in a clean, dry position, which is not subject to excessive shock or vibration and at least 2
metres away from pager systems or any other radio transmitting equipment.
The only items which are designed to be removed from the enclosure are the cable connectors. Ensure that all
electrical power is removed from the equipment before removing, inserting or connecting cables to these
connectors.