PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70
Doc No: GLT-215-7-1 Issue: 1.36 Author: NJ/TE DATE: 25/05/2017
16
4.6.5 PCB CONVENTIONAL SOUNDER CIRCUITS
The termination PCB has 2 conventional sounder circuit outputs, with a maximum capacity of 450 mA each. Please note that
conventional sounders should be wired as shown in the diagram below:
*The descriptions of sounders in this section also apply to flashers and combined sounder / flashers.
+
- -
+
+
- -
+
SND+
SND-
SOUNDER
SOUNDER
+
- -
+
SOUNDER
+
- -
+
SOUNDER
10K
End of
Line Resistor
Note: If non-polarized alarm devices (e.g. some types of old mechanical bell, or a relay) are used, then a diode will have to be
placed in line with the device to enable fault monitoring. They may also need a back EMF protection diode. (Symptoms: Chattering
sounder relays that don’t turn off).
+
- -
+
SND+
SND-
BELL
10K
End of
Line Resistor
+
- -
+
+
- -
+
BELL
BELL
CONNECTOR
BLOCK
POLARISING
DIODE
BACK EMF
DIODE
NC
NO
CM
RELAY
4.6.6 EVACS 16 VOICE ALARM SYSTEM
The Quatro panel can connect to the EVACS 16 system. It sees each channel of the EVACS as a voice sounder, so the panel has
control over the individual channels. They will be programmed as part of the usual ACTIONS programming for alert and evacuate
tones.
4.6.7 ADVANTAGES AND DISADVANTAGES OF DIFFERENT SOUNDER TYPES
SOUNDER TYPE
ADVANTAGE
DISADVANTAGE
Conventional
Wide range of devices.
Devices tend to be cheaper.
Immediate start / stop.
No quiescent current.
Needs extra cabling.
All sounders on each circuit start together
Stand-Alone Addressable or
Addressed Sounder Base
No extra cabling.
Individually started.
Tends to be more expensive.
Maximum 64 per loop.
Quiescent current relatively high.
Uses device address.
Associated (at detector address)
No extra cabling.
Doesn't occupy own address.
Individually started.
Not monitored trough protocol.
It needs a detector present to operate
individually.
Addressable Sounder Circuit
Controller
Wide range of devices.
Devices tend to be cheaper.
Can Add many sounder circuits to system.
Sounder circuit can be assigned to zone.
Needs Extra Cabling.
Needs External PSU.
Quiescent current high.
Uses device Address.
4k7
End of Line
Resistor
4k7
End of Line
Resistor
www.acornfiresecurity.com
www.acornfiresecurity.com