The AC Live (L), Earth (E) and Neutral (N) connections are marked on the power supply cage (top right of Figure 3). It is essential
that the mains Earth cable is connected to the PSU’s Earth terminal. The incoming mains cable should be kept separate from the
loop cables to help minimize mains interference.
Once the mains are connected, the panel door should be closed BEFORE turning on the mains power. This will protect the installer
from the chance of receiving an electric shock.
MAKE SURE ANY SPARE ENTRY HOLES ARE COVERED WITH PLASTIC GROMMETS.
It is advisable to apply power to the panel before connecting any devices, to check for correct operation, and to familiarise yourself
with the fire alarm panels controls.
5.6 CONNECTING THE BATTERIES
SOUNDER
CIRCUIT
DETECTION
LOOP
MAINS
IN
EARTH BAR
Figure 4: Battery location and connection details.
To calculate the exact requirement, use the equation in section 17. STANDBY BATTERY REQUIREMENTS.
The two batteries are wired in series.
The
+ve
of one battery is connected to the
red
battery lead.
The
–ve
of the other battery is connected to the
black
battery lead.
The –ve of the first battery is connected to the +ve of the second battery using the link wire supplied.
The battery leads will be factory-fitted to either the 5A PSE or to the motherboard (depending upon which version of the panel
has been supplied).
Recommended Battery Types:
Small / Lightly loaded systems – Powersonic 12V, 7 Ah; Heavily loaded systems, or systems requiring longer stand by –
Powersonic 12V 17 Ah. Other makes and sizes of battery may be suitable. Calculate the standby requirements to determine
the most suitable size of battery