6.3.5 ZASC – MI Sounder Control Module
The ZASC requires an external 24vdc power supply (as shown in the above diagram). The EOL for the sounder circuit is 10KΩ. When
using the ZASC make sure the PSU being used has a fault output relay, so that in the event of a power supply fault it is reported to
the control panel.
Note: All Power Supplies used on fire alarm systems MUST comply with EN54 part 4
6.3.6 ZAZM – MI Conventional Zone Module
The ZAZM powers the conventional zone from the addressable systems loop, so no external power supply is required. The EOL for
the zone is 6.2KΩ