PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70
Doc No: GLT-215-7-1 Issue: 1.36 Author: NJ/TE DATE: 25/05/2017
45
10.2 INSTALLER LEVEL (LEVEL 2)
Default Password 2222
PRIMARY SELECTION
SECONDARY SELECTION
TERTIARY SELECTION OR COMMENT
Loop
Autosearch
Searches for all devices on specified loop & displays:
VALID: xxx
DOUBLE ADDRESS: xxx
MODIFIED TYPE: xxx
Autosearch/ Reports
Lists the quantity of each type of device found
Autosearch/ Addresses
Address Map
Autocheck
Checks from start of loop (S) & then end of loop (R). Displays no. of devices
seen from each end of loop
LED Flash Setup
Device LEDs flash every 2s, (selected per loop)
Alarm Tone set up
Select 1 of 16 alarm tones to operate during alarm.
Loop Management
Selects which loops are fitted to the panel
Flasher Operation
Select whether flashers run until silence or until reset on a per loop basis
Engineering
Displays the communication quality for each loop
Zones
Zone edit
Edits zone text label & adds points to zone xxx in loop y
AutoAssign points
Assigns points to zones automatically. 25 devices per zone
Add point
Adds points to zone xxx in loop y
Points
Edit Point
Displays type, mode, analog value & text for each point, & allows text to be
edited
LED Setup
Sets the operation of the MKII detector flashing LEDs, and determines if a
platform sounder (sandwich sounder) is fitted
Toggling LED
Activates LED selected point to locate devices on a loop
Actions
New
Add a new cause & effect action. See Section 9.1
Modify
Modify an existing Action
New Logic
Add a new logic event action. See section 9.1.2
Modify Logic
Modify an existing logic action.
Class Change
Configure an I/O to act as a class change input
Disable relays
Configure an I/O to disable all relay outputs
Disable outputs
Configure an I/O to disable sounders & relays.
Logs
Faults
Event No Date/Time
Event Panel No/Loop No/Addr
Zone (if applicable) Text (if applicable)
Alarms
Event No Date/Time
Event Panel No/Loop No/Addr
Zone (if applicable) Text (if applicable)
Test
Event No Date/Time
Event Panel No/Loop No/Addr
Zone (if applicable) Text (if applicable)
All
Event No Date/Time
Event Panel No/Loop No/Addr
Zone (if applicable) Text (if applicable)
Erase
Erase Log (Yes / No)
General
Installation Name
Reference
Maintenance
Phone
Language
English / Espanyol/ Portuguese / Francais / Hungarian / Italian / Lietuviu /
Nederlands
Passwords
Level 1
Range 1 to 31
Password xxxx
Level 2
Current Password
New Password
Power supply
PSU Charger
Motherboard Charger
Disable Buzzer
Used to disable the panel buzzer during commissioning & maintenance
(F2 to bring up screen to toggle off LCD monitoring - for older PCBs)
Day-Night
Allows the installer to turn off delays at night time, and or disable relay
outputs during the day.
Delayed Mode
Two stage delay. Allows the user to set a short initial delay, followed by a
longer investigation delay.
www.acornfiresecurity.com
www.acornfiresecurity.com