PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70
Doc No: GLT-215-7-1 Issue: 1.36 Author: NJ/TE DATE: 25/05/2017
53
Faults Log (1024):
The screen will show the event number, the total no. of faults, the date, the
time, the type of fault that has occurred, the address of the device in fault, which
loop that it is in, and its location (i.e. text label). A maximum of 512 faults can be
stored. When the fault log is full, the next fault will over-write the first stored
fault, and so on.
FAULT <0123>/0512 01/07/15 12:34
Ter-STD (1.002) REMOVED
TEXT : Room 12C
[ - ] [ + ] [Exit ]
All types of faults are stored in this category. For a device fault the layout is almost identical to the Alarm log (see example). For a
general fault, line 2 is simply a description of the fault, and there is no information on line 3. The size of the Fault log is 1024.
Test Log (512):
This category indicates events that occur to devices contained in zones which are in the test mode. The LCD display is identical to
that of the Alarm log. 512 test events can be stored.
All Log (4096):
This category stores all Alarm and Fault events but not Test events. It has a capacity of 4096.
Note:
The Event Logs (also known as Reports) can be accessed by the Level 1 password (default 1111) or the Level 2 password
(default 2222). The only difference is that with the Level 2 password it is also possible to erase the entire contents of all 4 logs. This
should
NOT
be done during the normal use of the panel.
If a printer is fitted, refer to section 7.1.8 on how to print logs.