PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70
Doc No: GLT-215-7-1 Issue: 1.36 Author: NJ/TE DATE: 25/05/2017
54
15- STANDBY BATTERY REQUIREMENTS
15.1 PANEL & DEVICE CURRENT RATINGS
The Following Table shows the Quiescent, Fault & alarm currents of the main parts of a Premier QUATRO Fire Alarm System:
DEVICE
PRODUCT
CODE
I (MA)
QUIESCENT
I (MA)
FAULT
I (MA)
ALARM
MAX PER LOOP
Panels
Premier Quatro 1 Loop Analogue Addr Fire Alarm Panel
QT/1
140
140
190
N/A
Premier Quatro 2 Loop Analogue Addr Fire Alarm Panel
QT/2
190
190
240
N/A
Premier Quatro 3 Loop Analogue Addr Fire Alarm Panel
QT/3
240
240
300
N/A
Premier Quatro 4 Loop Analogue Addr Fire Alarm Panel
QT/4
300
300
360
N/A
Detectors
Fyreye MKII Addressable Optical Smoke Detector
MKII-AOP
0.5
N/A
5
250
Fyreye MKII Addressable Heat Detector
MKII-AHR
0.5
N/A
5
250
Fyreye MKII Fixed Temperature Heat Detector
MKII-AHF
0.5
N/A
5
250
Fyreye MKII Addressable Opto-Heat Detector
MKII-AOH
0.5
N/A
5
250
Call Points
Zeta Addressable Manual Call Point
ZT-CP3/AD
0.45
N/A
2.3
250
Zeta Addressable Weatherproof Manual Call Point
ZT-CP3/AD/WP
0.45
N/A
2.3
250
Sounders & Flashers
MKII Zeta Addressable Raptor Sounder
MKII-ZRAP
2.3
N/A
6.4
64
MKII Zeta Addressable Raptor Sounder Beacon
MKII-ZRAPB
2.3
N/A
20.3
20
Fyreye MKII Addressable Maxitone Sounder
MKII-AMT
0.65
N/A
7
32
Fyreye MKII Addressable Maxitone Sounder Flasher
MKII-AMTF
0.7
N/A
10.6
32
Fyreye MKII Addressable Maxitone Flasher
MKII-AMF
0.6
N/A
5.5
32
Fyreye MKII Addressable Miditone Sounder
MKII-AMD
0.65
N/A
4.5
64
Fyreye MKII Addressable Miditone Sounder Flasher
MKII-AMDSF
0.7
N/A
7.5
48
Fyreye MKII Addressable Miditone Flasher
MKII-AMDF
0.65
N/A
5.5
48
Fyreye MKII Addressable Xtratone Sounder
MKII-AXT
0.65
N/A
4.5
64
Fyreye MKII Addressable Xtratone Sounder Beacon
MKII-AXTB
2.3
N/A
20.3
20
Fyreye MKII Addressable Xtratone Flasher
MKII-AXF
0.6
N/A
5.5
48
Sandwich Sounder Base
MKII-SSB
0.65
N/A
5.5
64
Remote Indicator LEDs
MKII Addressable Remote LED Indicator (Wall)
MKII-ARL/W
0.5
N/A
5
32
MKII Addressable Remote LED Indicator (Ceiling)
MKII-ARL/C
0.5
N/A
5
32
Interfaces
Zeta Fyreye MKII Input Unit
ZAI-MI
1.0
1.25
3.6
64
Zeta Fyreye MKII Input Output Unit
ZAIO-MI
1.0
1.25
2
64
Zeta Fyreye MKII Input Output Unit – mains switching
ZAIO-MI /230
1.5
2.9
4.6
16
Zeta Fyreye MKII Sounder Control Module
ZASC-MI
0.6
0.6
0.8
64
Zeta Fyreye MKII Zone Monitor Module
ZAZM-MI
3.5
1.0
13.2
16
Wireless Transponder with LCD
WF-TRA-LCD
12
12
12
4
Wireless Transponder without LCD
WF-TRA-BFP
12
12
12
4
Special Mini Modules – Beam Detector
SMM/B
1.1
N/A
12
16
Conventional Sounders Via 2 Sounder Circuits(450mA
per Conv Circuit)
Zeta Conventional Maxitone Sounder
ZMT/8
0
N/A
15
N/A
Zeta Conventional Miditone Sounder
ZMD/8
0
N/A
15
N/A
Zeta Conventional Securetone Sounder
ZST/8
0
N/A
15
N/A
Zeta Conventional Megatone Sounder
ZIDC
0
N/A
200
N/A
Zeta Conventional Flasher
ZFL2RR
0
N/A
90
N/A
Zeta Conventional Sounder Flasher
ZLT/8RR
0
N/A
110
N/A
Zeta Conventional 6” Bells
ZTB6B/24
0
N/A
25
N/A
Zeta Conventional 8” Bells
ZTB8B
0
N/A
35
N/A
Conventional Detectors (via a Zone Monitor)
Fyreye Conventional Optical Detector
FEO2000
0.06
N/A
25
N/A
Fyreye Conventional Heat Detector (A1R)
FEHR2000
0.04
N/A
25
N/A
Fyreye Conventional Heat Detector (CS)
FEFH2000
0.04
N/A
25
N/A
Misc. Items
GSM COMMUNICATOR
GSM-COM
200
500
500
N/A
The Maximum per loop values given above are a guideline, based on the assumption that other devices on the loop do not cause