PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70
Doc No: GLT-215-7-1 Issue: 1.36 Author: NJ/TE DATE: 25/05/2017
5
1.6 FIRE ALARM SYSTEMS CODE OF PRACTICE
This manual is not designed to teach Fire Alarm System design. It is assumed that the System has been designed by a competent
person, and that the installer has an understanding of Fire Alarm System components and their use.
We strongly recommend consultation with a suitably qualified, competent person regarding the design of the Fire Alarm System.
The System must be commissioned and serviced in accordance with our instructions and the relevant National Standards. Contact
the Fire Officer concerned with the property at an early stage in case he has any special requirements.
If in doubt, read BS 5839-1:2013 “Fire Detection and Alarm Systems for buildings (Code of Practice for System Design, Installation,
commissioning and maintenance)” available from the BSI, or at your local reference library.
1.7 EQUIPMENT WARRANTY
If this equipment is not fitted and commissioned according to our guidelines, and the relevant National Standards, by an approved
and competent person or organization, the warranty may become void.
2- PANEL SPECIFICATION
2.1 FUNCTIONS REQUIRED BY EUROPEAN STANDARD EN54 PART 2
The Premier Quatro fire alarm control panel provides the following mandatory and optional functions as prescribed by the
European standard EN54 Part 2.
(a) Mandatory Functions
The mandatory functions and corresponding indications provided by this panel are:
fire alarm
fault warning
disabled
quiescent (when the CIE is powered by a power supply conforming to EN54-4 and no other functional condition is
indicated)
(
b) Optional Functions (Options with Requirements)
The options with requirements provided by this panel are:
Clause 7.8 - output to fire alarm devices (i.e. sounders)
Clause 7.11 - delays to outputs
Clause 8.3 - fault signals from points
Clause 9.5 - disablement of addressable points
Clause 10 – test Condition
(c) Other Functions outside EN54
RS232 Serial Output (Printer / Pager)
RS484 Network / Repeater connection
RS485 Modbus connection
TCP/IP (Ethernet) connection (Data log Alarm Manager)
NB the terms 'device' and 'point' are used interchangeably throughout this manual.