background image

EXPro Installation Manual 

 

 

Approved Document No: GLT-212-7-1 

 

Page 1 

Issue: 1.7   Author: MF/NRPJ   Date: 05/07/2021 

                                                              

 

 

 

 

 

INSTALLATION MANUAL 

Summary of Contents for Premier EXPro

Page 1: ...EXPro Installation Manual Approved Document No GLT 212 7 1 Page 1 Issue 1 7 Author MF NRPJ Date 05 07 2021 INSTALLATION MANUAL...

Page 2: ...NG THE ENCLOSURE TO THE WALL 9 ELECTRICAL CONNECTIONS 10 CONNECTING TO THE MAINS 10 CONNECTING THE BATTERIES 11 DETECTORS AND SOUNDERS 12 WIRING THE DETECTORS 12 WIRING THE SOUNDERS 12 OTHER CONNECTIO...

Page 3: ...SECOND STAGE ALARM 23 ABORT A SECOND STAGE ALARM 23 MANUAL MODE 24 RESET 24 FAULTS 24 ACCESS LEVELS 25 BATTERY CALCULATION 26 DEVICE CURRENT CONSUMPTION 26 EXPRO PANEL IN VARIOUS STATES 26 EXPANSION B...

Page 4: ...The Premier EXPRO is a 2 zone 1 area extinguishing panel It is designed to operate in Environmental Class A temperature range of 5 C to 40 C It has 2 zones dedicated to the extinguishing section Thes...

Page 5: ...the second crossed zone signalling an alarm Released condition The Premier EXPRO will enter the released condition bottle output activated within 1 second of establishing the activated condition or af...

Page 6: ...blement LEDs for most panel inputs and outputs For most functions more than one LED will light e g zone 1 fire and common fire The second stage sounder is pulsed during the activated condition and its...

Page 7: ...LED Colour Function Meaning Active 1st Stage Alarm Red Indicates when zone 1 or zone 2 is in an alarm condition Active 2nd Stage Alarm Red Indicates when zone 1 or zone 2 is in an alarm condition 1st...

Page 8: ...unders Stop 1st Stage Sounders Used to silence the 1st stage sounders Silence Buzzer Used to silence the internal buzzer in a fault or alarm condition Reset Used to reset the fire detection zone Reset...

Page 9: ...nts If any knockout is removed but subsequently not used then it should be covered up The 230Vac Mains cable must be fed into the enclosure via one of the cable entries at the top right corner of the...

Page 10: ...ins Disconnect Device EG switch or fuse point located near the fire alarm panel to allow a service engineer to power down the panel It should be an isolating double pole switch with contact separation...

Page 11: ...he BLACK battery lead The ve of the first battery is connected to the ve of the second battery using the link wire supplied Figure 4 Wiring the battery Although there are many sizes of suitable batter...

Page 12: ...7K end of line resistor Call points can NOT be connected to these zones A maximum of 32 detectors can be fitted to a zone Figure 5 Wiring the detectors WIRING THE SOUNDERS The Premier EXPRO has 2 firs...

Page 13: ...mally Open contacts then connect the 18K end of line resistor the 1k resistor as follows VE 18K 1K VE Figure 7 Wiring diagram for interfacing simple switched inputs 1ST STAGE 2ND STAGE FIRE RELAYS The...

Page 14: ...ttle Bottle Figure 8 Wiring diagram for the solenoid valve Bottle output EXTERNAL EQUIPMENT RELAY The Premier EXPRO has one volt free change over relay that operates AFTER the reset inhibit counter ha...

Page 15: ...Engineer 6 Relays 7 Change Time Zone This menu allows the user engineer to view the following information The voltage is an internal reference not the actual voltage measured on the terminals Expecte...

Page 16: ...Sounder 1B Disables sounder 1B Sounder 2 Disables the second stage sounder The panel will not enter the Activated condition if the second stage sounder is disabled Bottle Output Disables the bottle ou...

Page 17: ...uthor MF NRPJ Date 05 07 2021 The panel will automatically exit from a test condition after 15 minutes The test condition can be manually exited from the test menu Change Time Allows the user engineer...

Page 18: ...an DelayTimer Fan Duration Timer The Countdown Timer is the delay between the receipt of a second stage alarm and the gas being released It can be set from 0 to 60 seconds in 1 second increments To se...

Page 19: ...reset so that the system can be investigated by the responsible person to determine the cause of the release It can be set from 0 to 30 minutes To set the reset inhibit timer press enter option 5 Then...

Page 20: ...ition the installation engineer must therefore consider if it is acceptable for an output to be activated switched to the normally open condition in the event of the panel experiencing a total power f...

Page 21: ...alarm 1st stage sounders on 2nd stage alarm 1st and 2nd stage sounders on Release condition 1st and 2nd stage sounders on VERSION This menu display s the current software in the panel CHANGE PASSWORD...

Page 22: ...the fire alarm panel 3 Investigate to determine the cause of the alarm Look for the detector in the zone in alarm that signalled the fire The detector that signalled an alarm will have its RED ALARM...

Page 23: ...e second Zone the second stage alarm is initiated The second stage sounder will be pulsed on for 1 second then off for 1 second This will be repeated as the timer counts down The two zone alarm LEDs w...

Page 24: ...NOT be reset from a fault condition All faults are non latching so when a fault clears from the panel it will be automatically cleared from the display In the event of an alarm in the peripheral fire...

Page 25: ...nce buzzer Reset panel Disable sections of the system Put the panel into test mode Set the default relay states View logs 3a Installer engineer Engineer level password default 1111 Reset logs and or p...

Page 26: ...Max EXTERNAL DEVICES Item Quiescent Alarm Optical 100uA 35mA Heat 50uA 35mA Maxitone Sounder 0mA 25mA DETERMINING BATTERY SIZE To calculate the required battery backup capacity we use the equation Mi...

Page 27: ...andby time The first stage alarm sounds for a minimum of 30 minutes The bottle output activates 1A for 5 minutes ISBY 57mA 0 057A TSBY 48h IALM Premier EXPro Alm 8x Maxitone Sounder 1 detector in alar...

Page 28: ...r 6 Abort Abort Input Abort Call point or switch 18k EOL 1K trigger resistor 7 S1A First Stage Sounder Circuit A Conventional sounder flasher bell 29 5V nominal 150mA max 8 S1B First Stage Sounder Cir...

Page 29: ...5V DC 31 5V DC Charger Voltage 27 6VDC 20 C Charger Capacity 3 4Ah 7 2Ah Battery Deep Discharge Protection Battery Shutdown at 20 3V battery terminals Number of Zones 2 Crossed Zones Maximum devices p...

Page 30: ...uipment FIRE ALARM CONTROL SECTION As well as meeting the requirements of EN54 2 1998 A1 A2 the Premier EXPro also has the following options with requirements Clause 7 8 Output to fire alarm devices O...

Page 31: ...te 05 07 2021 The extinguishing control section also has the following ancillary functions not required by the Standard Serial repeater output Automatic mode relay Manual only mode relay Abort relay F...

Page 32: ...d alarm info Added Timer Diagram Added Max Min info to spec table Added Compatible Eqpt to terminal list Reworded SND2 Disablement description Added Zone voltage description menu item Corrected IMAX A...