PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70
Doc No: GLT-215-7-1 Issue: 1.36 Author: NJ/TE DATE: 25/05/2017
23
The connection for the detectors bases is made as follows:
Terminal L1IN is –ve (Blue)
Terminal L2 is +ve (Brown)
These are the only two connections required.
Deep Base MKII-CB/D
Common Base MKII-CB
6.3.3 ZAI - MI Input Module
The end of line resistor value is 20KΩ and the trigger resistor value is 1kΩ.
6.3.4 ZAIO – MI Input/output Module
The end of line resistor value is 20KΩ and the trigger resistor value is 1KΩ.