PREMIER QUATRO USER MANUAL, MAINTENANCE GUIDE & LOG BOOK (Fyreye MKII)
#Doc No. GLT-215-7-2
PAGE 8
Issue: 1.08 Author: TE/NJ Date: 26/05/2017
5. THE FIRE CONDITION
5.1 HOW THE QUATRO INDICATES AN ALARM
When the Panel is set into alarm by a Detector or
Manual Call Point located in a zone that is not already in
alarm it will: -
Light the COMMON FIRE LED and appropriate
ZONE FIRE LED(s) on the front of its enclosure.
Display fires from any zone on the LCD display.
Sound the Internal buzzer.
Start the Alarm Sounders and Auxiliary
Outputs, (unless a delay has been programmed).
The building evacuation procedure should now be
followed.
FIRST ALARM: Z015 – SECOND FLOOR
LAST ALARM : Z025 – FOURTH FLOOR
ZONES IN FIRE : 003 POINTS IN FIRE : 005
PRESS ◄ OR ► TO SCROLL
FIRST ALARM: Z015 – SECOND FLOOR
LAST ALARM : Z025 – FOURTH FLOOR
002/005-08:10 Z086 – STAIR WELL
MKII-AOP (2.4.124) - ROOM 101
More information about fires in any zone can be seen on the LCD by using the MENU NAVIGATION buttons to scroll the fire data. In
the above example, 5 points (i.e. detectors or call points) are in fire. These are located in 3 different zones. The first alarm occurred
in zone 15 and the most recent alarm occurred in zone 25. The 2nd point is located in zone 86 (STAIRWELL). The address label of this
point is ROOM 101. It is on panel number 2, loop number 4 and at address 124. The point, which is an optical detector, was
triggered at the time of 08:10.
IMPORTANT NOTE:
If a zone has been disabled, it cannot be triggered into Alarm. This should be remembered when disabling part
of the system (see Disablements in Section 7).
5.2 HOW TO TURN OFF THE ALARM SOUNDERS
The Alarm Sounders may be silenced by turning the control key to CONTROL ENABLE position and momentarily pressing
the START/STOP SOUNDERS button.
The Alarm Sounders will cease to sound* but the light(s) for the Zone(s) in Alarm and the red COMMON FIRE light will stay lit. The
Auxiliary Outputs will remain active. (The Panels internal buzzer can also be silenced by pressing the SILENCE BUZZER button).
*Addressable loop sounders will stop within 2 seconds. Sounder bases can take up to 10 seconds to stop. If the START/STOP button
is pressed again during this time, the panel will start the sounders again.
5.3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE
If another detection Zone is activated after the Alarm Sounders have been silenced, the panel will: -
Restart the sounders
Light the Zone Fire LED(s) for any new Zone(s) in alarm
Keep the LED(s) for the previous Zone(s) in fire, and General Fire, lit.