PREMIER QUATRO USER MANUAL, MAINTENANCE GUIDE & LOG BOOK (Fyreye MKII) 

#Doc No. GLT-215-7-2 

 

PAGE 8

 

 

Issue: 1.08   Author: TE/NJ     Date: 26/05/2017

 

 

5. THE FIRE CONDITION 

5.1 HOW THE QUATRO INDICATES AN ALARM 

 

 

When the Panel is set into alarm by a Detector or 
Manual Call Point located in a zone that is not already in 
alarm it will: - 

 

Light the COMMON FIRE LED and appropriate 
ZONE FIRE LED(s) on the front of its enclosure. 

 

Display fires from any zone on the LCD display. 

 

Sound the Internal buzzer. 

 

Start the Alarm Sounders and Auxiliary 

 

Outputs, (unless a delay has been programmed). 

 

The building evacuation procedure should now be 
followed. 

FIRST ALARM: Z015 – SECOND FLOOR 
LAST ALARM : Z025 – FOURTH FLOOR 
ZONES IN FIRE : 003 POINTS IN FIRE : 005 
PRESS ◄ OR ► TO SCROLL 

 

FIRST ALARM: Z015 – SECOND FLOOR 
LAST ALARM : Z025 – FOURTH FLOOR 
002/005-08:10 Z086 – STAIR WELL 
MKII-AOP (2.4.124) - ROOM 101 

 

More information about fires in any zone can be seen on the LCD by using the MENU NAVIGATION buttons to scroll the fire data. In 
the above example, 5 points (i.e. detectors or call points) are in fire. These are located in 3 different zones. The first alarm occurred 
in zone 15 and the most recent alarm occurred in zone 25. The 2nd point is located in zone 86 (STAIRWELL). The address label of this 
point is ROOM 101. It is on panel number 2, loop number 4 and at address 124. The point, which is an optical detector, was 
triggered at the time of 08:10. 

IMPORTANT NOTE:

 If a zone has been disabled, it cannot be triggered into Alarm. This should be remembered when disabling part 

of the system (see Disablements in Section 7). 

5.2 HOW TO TURN OFF THE ALARM SOUNDERS 

 

The Alarm Sounders may be silenced by turning the control key to CONTROL ENABLE position and momentarily pressing 
the START/STOP SOUNDERS button. 

The Alarm Sounders will cease to sound* but the light(s) for the Zone(s) in Alarm and the red COMMON FIRE light will stay lit. The 
Auxiliary Outputs will remain active. (The Panels internal buzzer can also be silenced by pressing the SILENCE BUZZER button). 

*Addressable loop sounders will stop within 2 seconds. Sounder bases can take up to 10 seconds to stop. If the START/STOP button 
is pressed again during this time, the panel will start the sounders again. 

5.3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 

If another detection Zone is activated after the Alarm Sounders have been silenced, the panel will: - 

 

Restart the sounders 

 

Light the Zone Fire LED(s) for any new Zone(s) in alarm 

 

Keep the LED(s) for the previous Zone(s) in fire, and General Fire, lit. 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for Premier Quatro QT/1P

Page 1: ...NCE GUIDE LOG BOOK Fyreye MKII Firmware Versions PANEL 1 84 LOOP CARD 3 70 MKII PROTOCOL ONE TO FOUR LOOPS ANALOGUE ADDRESSABLE FIRE ALARM PANEL USER MANUAL MAINTENANCE GUIDE LOG BOOK www acornfiresec...

Page 2: ...CATES AN ALARM 8 5 2 HOW TO TURN OFF THE ALARM SOUNDERS 8 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 8 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP TO EVACUATE THE BUILDING 9 5 5 RESETTING...

Page 3: ...ivate a smoke detector If anything is found try to clear the room by opening a window If there is a fire discovered either attempt to douse it with a fire extinguisher if suitably trained or call the...

Page 4: ...the local fire brigade called according to the company evacuation procedure 2 An Alarm can be raised from Smoke or Heat Detectors or manually by a person operating a Manual Call Point 3 To split the...

Page 5: ...ensure that cleaning maintenance or building work does not interfere with the functioning and reliability of the fire alarm system 47 2 h 9 Ensure any changes to the system are recorded with updated d...

Page 6: ...ch Mode cage INPUT Voltage 30 5 VAC Charger Voltage 27 6V off load adjusted with VR1 Battery Voltage 25 27V Every Five Years to be carried out by authorised service personnel only Carry out a complete...

Page 7: ...the panel next to the enclosure s lock If the panel is located in a position where the general public have access this key must be removed from the panel and placed where it can be easily accessed by...

Page 8: ...cel programmed delays and test the LEDs and LCD The user can also enter the test mode which permits points in selected zone s to be tested without causing the alarm to be raised throughout the buildin...

Page 9: ...2nd point is located in zone 86 STAIRWELL The address label of this point is ROOM 101 It is on panel number 2 loop number 4 and at address 124 The point which is an optical detector was triggered at...

Page 10: ...ers Note If ALL of the Alarm Sounders have been disabled pressing the STOP START BUTTON will have NO effect 5 5 RESETTING THE PANEL Check the cause of the alarm activation If the cause of the alarm wa...

Page 11: ...t of this are 20 LEDs which are used to indicate Zone Faults Disablement Test in Zones 1 20 COMMON FAULT The Common fault LED is lit for all types of fault SUPPLY FAULT This indicates a loss of Mains...

Page 12: ...ght along with the zone that contains that sounder Because the sounder is addressable any fault will be indicated as a device fault 6 2 WHAT TO DO IF A FAULT CONDITION OCCURS If a fault occurs the res...

Page 13: ...r disabling the zone selecting Enable instead of Disable 7 3 TO DISABLE A POINT Rather than disable an entire zone it is often useful to just disable one or more input devices detector call point or i...

Page 14: ...FIRE ALARM SYSTEM SUMMARY FIRE ZONE INFORMATION ZONE NO LOOP NO ZONE DESCRIPTION A brief description of all the rooms and areas contained in each zone NO OF DETECTORS NO OF MCPS NO OF SOUNDERS NO OF I...

Page 15: ...ZONE NO LOOP NO ZONE DESCRIPTION A brief description of all the rooms and areas contained in each zone NO OF DETECTORS NO OF MCPS NO OF SOUNDERS NO OF I OS 37 38 39 40 41 42 43 44 45 46 47 48 49 50 5...

Page 16: ...NO ZONE DESCRIPTION A brief description of all the rooms and areas contained in each zone NO OF DETECTORS NO OF MCPS NO OF SOUNDERS NO OF I OS 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 10...

Page 17: ...ONE DESCRIPTION A brief description of all the rooms and areas contained in each zone NO OF DETECTORS NO OF MCPS NO OF SOUNDERS NO OF I OS 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 1...

Page 18: ...ONE DESCRIPTION A brief description of all the rooms and areas contained in each zone NO OF DETECTORS NO OF MCPS NO OF SOUNDERS NO OF I OS 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 1...

Page 19: ...ONE DESCRIPTION A brief description of all the rooms and areas contained in each zone NO OF DETECTORS NO OF MCPS NO OF SOUNDERS NO OF I OS 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 2...

Page 20: ...contained in each circuit NO OF SOUNDERS NO OF BELLS 1 2 INPUTS OUTPUTS INFORMATION ZONE NO LOOP NO DESCRIPTION OF INPUTS AND OUTPUTS CONNECTED TO LOOP WHAT HAPPENS WHEN ACTIVATED FIRE FAULT RELAYS IN...

Page 21: ...ptable ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97 14 56 98 15 57 99 16 5...

Page 22: ...175 217 134 176 218 135 177 219 136 178 220 137 179 221 138 180 222 139 181 223 140 182 224 141 183 225 142 184 226 143 185 227 144 186 228 145 187 229 146 188 230 147 189 231 148 190 232 149 191 233...

Page 23: ...ptable ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97 14 56 98 15 57 99 16 5...

Page 24: ...175 217 134 176 218 135 177 219 136 178 220 137 179 221 138 180 222 139 181 223 140 182 224 141 183 225 142 184 226 143 185 227 144 186 228 145 187 229 146 188 230 147 189 231 148 190 232 149 191 233...

Page 25: ...ptable ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97 14 56 98 15 57 99 16 5...

Page 26: ...175 217 134 176 218 135 177 219 136 178 220 137 179 221 138 180 222 139 181 223 140 182 224 141 183 225 142 184 226 143 185 227 144 186 228 145 187 229 146 188 230 147 189 231 148 190 232 149 191 233...

Page 27: ...ptable ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97 14 56 98 15 57 99 16 5...

Page 28: ...175 217 134 176 218 135 177 219 136 178 220 137 179 221 138 180 222 139 181 223 140 182 224 141 183 225 142 184 226 143 185 227 144 186 228 145 187 229 146 188 230 147 189 231 148 190 232 149 191 233...

Page 29: ...work or panel conditions This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1 recommends that fi...

Page 30: ...K Fyreye MKII Doc No GLT 215 7 2 PAGE 29 Issue 1 08 Author TE NJ Date 26 05 2017 MAINTENANCE WORK DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQUIRED SIGNED...

Page 31: ...eye MKII Doc No GLT 215 7 2 PAGE 30 Issue 1 08 Author TE NJ Date 26 05 2017 MAINTENANCE WORK CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQUIRED SI...

Page 32: ...1 08 Author TE NJ Date 26 05 2017 UNWANTED FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN CE FINDINGS CATEGORY...

Page 33: ...Author TE NJ Date 26 05 2017 UNWANTED FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN CE FINDINGS CATE...

Page 34: ...7 2 PAGE 33 Issue 1 08 Author TE NJ Date 26 05 2017 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KNOWN ACTION REQUIR...

Page 35: ...PAGE 34 Issue 1 08 Author TE NJ Date 26 05 2017 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE IF KNOWN ACTION...

Page 36: ...an signal an alarm condition and indicate the correct zone and text message on the fire alarm panel The Sound pressure level throughout the building should be checked for compliance with the recommend...

Page 37: ...onsible complies to the best of my our knowledge and belief with the recommendations of section 2 of BS 5839 1 2013 for the system category described below except for the variations if any stated in t...

Page 38: ...ided to the user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recommended that installation and commissioning be undertaken...

Page 39: ...recommendations of BS 5839 1 2013 except for the variations if any stated in this certificate Name Block Letters Position Signature Date For on behalf of Address The extent of liability of the signat...

Page 40: ...ent operates correctly Installation work is as far as can be reasonably ascertained of an acceptable standard The entire system has been inspected and tested in accordance with the recommendations of...

Page 41: ...l installation work appears to be satisfactory The system is capable of giving a fire alarm signal The facility for remote transmission of alarms to an alarm receiving centre operates correctly Delete...

Reviews: